| Plan Review Notes For Permit 04010028 |
| Permit Number |
04010028 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-19 00:00:00 | ************ UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE LOAD SHOWN FOR AHU | | | ON PANEL SCHEDULE, SHOWS 5KW, YET LOAD | | | CALCULATIONS DO NOT CORRELATE. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALC FOR EACH | | | PANEL AND THEN SERVICE. | | | PLEASE SEE LOAD SHOWN FOR WAHT APPEARS | | | TO BE EACH PANEL @ 113 A'S, YET OCP IS | | | 100A'S? | | | | | | 3)NOTE: PLEASE SEE PANELS, SHOWN AS 42 | | | CIR, 150A PANELS ARE NOT MADE W/ 42 CIR. | | | | | | 4)NOTE: PLEASE SEE MISSING FRONT AND | | | REAR RECEPTS PER 210.52E | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPT FOR | | | A/C COND UNIT. 210.63. RECEPT FOR REAR | | | OF DWELLING MAY MEET REQUIREMENT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|