Plan Review Notes
Plan Review Notes For Permit 04010028
Permit Number 04010028
Review Stop E
Sequence Number 2
Notes
Date Text
2004-02-19 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE SEE LOAD SHOWN FOR AHU
 ON PANEL SCHEDULE, SHOWS 5KW, YET LOAD
 CALCULATIONS DO NOT CORRELATE.
  
 2)NOTE: PLEASE SHOW LOAD CALC FOR EACH
 PANEL AND THEN SERVICE.
 PLEASE SEE LOAD SHOWN FOR WAHT APPEARS
 TO BE EACH PANEL @ 113 A'S, YET OCP IS
 100A'S?
  
 3)NOTE: PLEASE SEE PANELS, SHOWN AS 42
 CIR, 150A PANELS ARE NOT MADE W/ 42 CIR.
  
 4)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS PER 210.52E
  
 5)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C COND UNIT. 210.63. RECEPT FOR REAR
 OF DWELLING MAY MEET REQUIREMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]