| Plan Review Notes For Permit 04010014 |
| Permit Number |
04010014 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLA. ADMIN. CODE | | | FLA. STATUTES. | | | | | | 1) SHT 6/7 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. | | | A) MASTER BATH - W/C SHALL BE VENTED BY | | | WET VENT AND BE TIED INTO THE BATHROOM | | | GROUP. PUMPING ACTION FROM WASH MACHINE | | | WILL EFFECT WATER CLOSET TRAP SEAL. | | | B) MASTER BATH - NO DRY HORIZONTAL DRY | | | VENTS ALLOWED. SECTION 905.3 | | | C) TUB NOT VENTED IN SECOND BATH. SEC- | | | TION 901.2.1 | | | D) SEE RED LINE CORRECTIONS ON PLUMBING | | | LAYOUT AND RISER DIAGRAM. | | | 2) PLANS SUBMITTED BY AN ENGINEER SHALL | | | BE SIGNED, SEALED AND DATED BY THE | | | ENGINEER. FAC 61G15-23.002(1) & FS 471 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|