Plan Review Notes
Plan Review Notes For Permit 04010014
Permit Number 04010014
Review Stop M
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00DENIED:
 MECHANICAL PLANS DO NOT MATCH BUILDING
 FLOOR PLAN.THE MECHANICAL PLAN SHOWS
 THE WALL BETWEEN THE AHU AND THE
 RESIDENCE HAVING A 1HR RATING.PLEASE
 REVISE MECHANICAL PLAN TO REFLECT THAT
 OF THE BUILDING FLOOR PLAN.
  
 RETURN AIR DUCT IS NOT SIZED PROPERLY.
 PLEASE SEE THE ATTACHED SCHEDULE FOR
 REQUIRED RETURN AIR.PLEASE NOTE THE
 MASTER BEDROOM RETURN AIR IS BASED UPON
 THE TOTAL OF SUPPLY AIR TO THE MASTER
 SUITE.PLAN INDICATES A 10" SUPPLY
 WHICH WOULD REQUIRE A MINIMUM OF 13"
 RETURN.
  