| Plan Review Notes For Permit 04010014 |
| Permit Number |
04010014 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-14 00:00:00 | DENIED: | | | MECHANICAL PLANS DO NOT MATCH BUILDING | | | FLOOR PLAN.THE MECHANICAL PLAN SHOWS | | | THE WALL BETWEEN THE AHU AND THE | | | RESIDENCE HAVING A 1HR RATING.PLEASE | | | REVISE MECHANICAL PLAN TO REFLECT THAT | | | OF THE BUILDING FLOOR PLAN. | | | | | | RETURN AIR DUCT IS NOT SIZED PROPERLY. | | | PLEASE SEE THE ATTACHED SCHEDULE FOR | | | REQUIRED RETURN AIR.PLEASE NOTE THE | | | MASTER BEDROOM RETURN AIR IS BASED UPON | | | THE TOTAL OF SUPPLY AIR TO THE MASTER | | | SUITE.PLAN INDICATES A 10" SUPPLY | | | WHICH WOULD REQUIRE A MINIMUM OF 13" | | | RETURN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|