Plan Review Notes
Plan Review Notes For Permit 04010014
Permit Number 04010014
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-08 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES FOR
 CODE COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE A/C AREA SHOWN IN THE TOTAL AREA
 BOX ON SHEETS 5/5,7/7,LOAD CALCS AND
 PERMIT APPLICATION DO NOT
 CORRELATE.PLEASE CHANGE TO REFLECT THE
 CORRECT SQUARE FOOTAGES.
  
 2} THE ELECTRICAL NOTES ON SHEET 5/7
 SHOULD REFLECT THE FOLLOWING:
 #2 SHOULD REFERENCE THE FLORIDA
 BUILDING CODE,NOT SFBC.
 #4 SHOULD INDICATE THE SMOKE DETECTORS
 BEING FED FROM AN ARC FAULT PROTECTED
 CIRCUIT PER 210.12.
 #7 REFERENCES AN OUT OF DATE ARTICLE,
 PLEASE REFER TO 2002 NEC.
 #17 SHOULD REFER TO ALL OUTLETS NOT
 JUST RECEPTACLES,SEE 210.12 AND ALSO
 ART. 100 FOR DEFINITION OF "OUTLET".
  
 3} THE GARAGE MUST HAVE A GFI RECEPTACLE
 PER210.8(A)(2).
  
 4} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  