| 2004-02-06 00:00:00 | *****CORRECTIONS***** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE |
| | A PERMIT CAN BE ISSUED FS713.13.THE |
| | NOC PROVIDED IS EXPIRED (OVER 90 DAYS |
| | WITHOUT COMMENCING WORK). |
| | |
| | 2.)IF ALL PRODUCT APPROVALS REQUIRED |
| | ARE NOT PROPERLY SUBMITTED BEFORE PERMIT |
| | ISSUANCE, SEPARATE PERMITS FOR THOSE |
| | ITEMS WILL BE REQUIRED. |
| | |
| | 3.)HAVE ANY NEW REVISED SHEETS STAMPED |
| | BY HISTORIC BEFORE RESUBMITTAL. |
| | |
| | 4.)THE SQUARE FOOTAGE ON THE |
| | APPLICATION DOES NOT MATCH THE PLAN. |
| | REVISE. |
| | |
| | 5.)ADDITIONAL FEES DUE, $516.43, SEE |
| | ATTACHED BZ235304 (VALUE ADJUSTMENT). |
| | |
| | 6.)HAVE AN INDIVIDUAL SIGN THE |
| | OWNER/AGENT LINE OF THE ENERGY CALC, |
| | FBC13-101.2. |
| | |
| | 7.)PROVIDE A SOILS INVESTIGATION |
| | REPORT, FBC1804.2.2. |
| | |
| | 8.)PROVIDE THE RECEIPT FOR THE IMPACT |
| | FEES. |
| | |
| | 9.)FLORIDA STATEWIDE OR SITE SPECIFIC |
| | PRODUCT APPROVALS REQUIRED IN ADDITION |
| | TO THE TEST REPORTS.PRINT THE COVER |
| | SHEET FROM THE WEBSITE, CIRCLE THE |
| | PRODUCT YOU ARE USING. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 10.) THE PRODUCT APPROVALS FOR THE |
| | SINGLE HUNG WINDOW ARE NOT LEGIBLE. |
| | YOU MAY BE ABLE TO DOWNLOAD THIS REPORT |
| | FROM EITHER WWW.FLORIDABUILDING.ORG OR |
| | WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING |
| | CODE COMPLIANCE, PRODUCT CONTROL SEARCH) |
| | |
| | 11.) THE FOLLOWING PRODUCT APPROVALS |
| | ARE REQUIRED: FRONT DOOR, MULLIONS, |
| | ARCH FIXED GLASS, GARAGE DOOR, ROOF |
| | TILE, SLIDING GLASS DOOR, IMPACT |
| | PROTECTION, SINGLE HUNG WINDOW, ROOF. |
| | |
| | 12.) THE DOOR PRODUCT APPROVAL IS FOR |
| | INSWING, THE DOOR IS SHOWN AS AN |
| | OUTSWING. |
| | |
| | 13.)IMPACT PROTECTION REQUIRED |
| | FBC1606.1.4.SUBMIT PRODUCT APPROVALS |
| | AS WELL AS THE HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE ATTACHED.IF THIS |
| | IS NOT SUBMITTED A SEPARATE PERMIT WILL |
| | BE REQUIRED FOR SHUTTERS. |
| | |
| | 14.)29" CLEARANCE REQUIRED FOR THE |
| | BATHROOM DOOR TO COMPLY WITH FBC11-11(1) |
| | |
| | 15.) SPECIFY ATTIC ACCESS TO COMPLY WITH |
| | FBC2309.6. |
| | |
| | 16.)ROOF DOWNSPOUTS TO COMPLY WITH |
| | FBC1503.4.4. |
| | |
| | 17.)CONFIRM THAT THE WINDOW BUCK |
| | DETAIL IS CONSISTENT WITH THE PRODUCT |
| | APPROVAL, WHICH IS ILLEGIBLE.IT |
| | APPEARS TO REQUIRE A 1 1/2" EMBEDMENT, |
| | THE DETAIL PROVIDE STATES "PER PRODUCT |
| | APPROVAL" BUT ALSO GIVES A TAPCON LENGTH |
| | OF 2" WHICH WOULD NOT COMPLY. |
| | |
| | 18.)I COULD NOT FIND THE SIMPSON |
| | HUS26 IN THE HIGH WIND CATALOG WHICH |
| | DOES NOT INCLUDE THE STRESS INCREASE |
| | FOR STEEL.ADDRESS. |
| | |
| | 19.)SPECIFY TRUSS CONNECTOR (WALL |
| | SECTION, SHEET 2). |
| | |
| | 20.)SHEET 7 SPECIFIES A 2' OVERHANG |
| | AND A SQUARE FOOT AREA NOT CONSISTENT |
| | WITH THE PLAN. |