2004-02-06 00:00:00*****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED FS713.13.THE
 NOC PROVIDED IS EXPIRED (OVER 90 DAYS
 WITHOUT COMMENCING WORK).
  
 2.)IF ALL PRODUCT APPROVALS REQUIRED
 ARE NOT PROPERLY SUBMITTED BEFORE PERMIT
 ISSUANCE, SEPARATE PERMITS FOR THOSE
 ITEMS WILL BE REQUIRED.
  
 3.)HAVE ANY NEW REVISED SHEETS STAMPED
 BY HISTORIC BEFORE RESUBMITTAL.
  
 4.)THE SQUARE FOOTAGE ON THE
 APPLICATION DOES NOT MATCH THE PLAN.
 REVISE.
  
 5.)ADDITIONAL FEES DUE, $516.43, SEE
 ATTACHED BZ235304 (VALUE ADJUSTMENT).
  
 6.)HAVE AN INDIVIDUAL SIGN THE
 OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-101.2.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 8.)PROVIDE THE RECEIPT FOR THE IMPACT
 FEES.
  
 9.)FLORIDA STATEWIDE OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED IN ADDITION
 TO THE TEST REPORTS.PRINT THE COVER
 SHEET FROM THE WEBSITE, CIRCLE THE
 PRODUCT YOU ARE USING.
 WWW.FLORIDABUILDING.ORG
  
 10.) THE PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOW ARE NOT LEGIBLE.
 YOU MAY BE ABLE TO DOWNLOAD THIS REPORT
 FROM EITHER WWW.FLORIDABUILDING.ORG OR
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE COMPLIANCE, PRODUCT CONTROL SEARCH)
  
 11.) THE FOLLOWING PRODUCT APPROVALS
 ARE REQUIRED: FRONT DOOR, MULLIONS,
 ARCH FIXED GLASS, GARAGE DOOR, ROOF
 TILE, SLIDING GLASS DOOR, IMPACT
 PROTECTION, SINGLE HUNG WINDOW, ROOF.
  
 12.) THE DOOR PRODUCT APPROVAL IS FOR
 INSWING, THE DOOR IS SHOWN AS AN
 OUTSWING.
  
 13.)IMPACT PROTECTION REQUIRED
 FBC1606.1.4.SUBMIT PRODUCT APPROVALS
 AS WELL AS THE HURRICANE SHUTTER
 INSTALLATION SCHEDULE ATTACHED.IF THIS
 IS NOT SUBMITTED A SEPARATE PERMIT WILL
 BE REQUIRED FOR SHUTTERS.
  
 14.)29" CLEARANCE REQUIRED FOR THE
 BATHROOM DOOR TO COMPLY WITH FBC11-11(1)
  
 15.) SPECIFY ATTIC ACCESS TO COMPLY WITH
 FBC2309.6.
  
 16.)ROOF DOWNSPOUTS TO COMPLY WITH
 FBC1503.4.4.
  
 17.)CONFIRM THAT THE WINDOW BUCK
 DETAIL IS CONSISTENT WITH THE PRODUCT
 APPROVAL, WHICH IS ILLEGIBLE.IT
 APPEARS TO REQUIRE A 1 1/2" EMBEDMENT,
 THE DETAIL PROVIDE STATES "PER PRODUCT
 APPROVAL" BUT ALSO GIVES A TAPCON LENGTH
 OF 2" WHICH WOULD NOT COMPLY.
  
 18.)I COULD NOT FIND THE SIMPSON
 HUS26 IN THE HIGH WIND CATALOG WHICH
 DOES NOT INCLUDE THE STRESS INCREASE
 FOR STEEL.ADDRESS.
  
 19.)SPECIFY TRUSS CONNECTOR (WALL
 SECTION, SHEET 2).
  
 20.)SHEET 7 SPECIFIES A 2' OVERHANG
 AND A SQUARE FOOT AREA NOT CONSISTENT
 WITH THE PLAN.