| 2004-05-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) FROM PREVIOUS REVIEW: COMMENTS NOT |
| | ADDRESSED TO CODE SATISFACTION. NUMBER |
| | OF COMMENT FROM FIRST REVIEW TO STAY THE |
| | SAME TO AVOID CONFUSION. |
| | 2) IF TOILET ROOMS ARE PROVIDED, THEN |
| | EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY WITH 11-4.22. SUBMIT A DE- |
| | TAIL SHOWING COMPLIANCE WITH 11-4.16, |
| | 11-4.19, AND 11-4.22 AND ALL SUBSECTIONS |
| | - SECTION 11-4.1.3(11). RESPONSE NOTED, |
| | BUT HEIGHT OF TOILET NOT SHOWN 11-4.16.3 |
| | CLEAR FLOOR SPACE/TURNING AREA 11-4.16.2 |
| | GRAB BARS NOT SHOWN IN TOILET ROOM BY |
| | KITCHEN 11-4.16.4, CLEAR FLOOR SPACE FOR |
| | LAV 11-4.19.3, EXPOSED PIPES & SURFACES |
| | 11-4.19.4, DOORS SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE FOR ANY FIXTURE |
| | 11-4.22.2(1). |
| | 3) SHT E-1 SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. THE ACCESSI- |
| | BLE TOILET ROOM SHOULD BE LOCATED ON THE |
| | LEFT SIDE OF THE BLDG. DRAIN. IF THE |
| | BUILDING HAS TWO BLDG. DRAINS THEN A C/O |
| | IS REQUIRED AS EACH BLDG. DRAIN EXITS |
| | THE BLDG. SECTION 708.3.5 - REMOVE THE |
| | DRINKING FOUNTAIN FROM THE SANT. RISER |
| | DIAGRAM, HAND DRAWN CHANGES TO A SIGNED |
| | AND SEALED SET OF PLANS IS NOT APPROVED. |
| | 4) KITCHEN SINK SHALL COMPLY WITH SECT- |
| | ION 11-4.24 AND ALL SUBSECTIONS. CLEAR |
| | FLOOR SPACE FOR SINK IS NOT SHOWN. SEE |
| | SECTION 11-4.24.5 |
| | NEW COMMENT...................... |
| | 1B) ENGINEERS SHALL SIGN PLAN WITH A |
| | SIGNATURE. PER FBPE'S RULING INITIALS |
| | ARE NOT ACCEPTABLE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |