Plan Review Notes
Plan Review Notes For Permit 04010010
Permit Number 04010010
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-28 00:00:00********** UNSAT *********
  
 PLEASE SEE SOME NOTES FORM FIRST REVIEW
 NOT DONE AND THERE ARE ALOS NEW NOTES.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
 PANEL SCHEDULE MUST SHOWS CIRCUIT #'S,
 OCP, AWG ETC.
  
 2)NOTE: PLEASE SEE NEC FOR DERATING
 OF INDIVIDUAL BRANCH CIRCUITS IN 1"
 SCH80 PVC CONDUIT. 240,TABLES ETC.
  
 3)NOTE: PLEASE SHOW A/C EQUIPMENT ON
 ELECTRICAL PLANS ALONG WITH DISC AS
 REQ'D PER 440.11.
  
 4)NOTE: PLEASE SHOW RECEPTS REQ'D UNDER
 210.63 FOR A/C EQUIPMENT.
  
 5)NOTE: PLEASE SEE BLDG USE IS BEING
 CHANGED FROM RESIDENCE TO COMM.
 PLEASE SEE TWO METER SYSTEM MUST BE
 REMOVED AND BE INSTALLED BACK TO SINLGE
 METER INSTALLATION.
 PLEASE ADJUST SERVICE ACCORD.
  
 6)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 7)NOTE: PLEASE HAVE ENGINEER SIGN WITH
 COMPLETE "SIGNATURE" AS SHOWN ON LICENSE
 /RAISED SEAL AS REQ'D UNDER FS 471.025
 INITIALS ARE NOT ACCEPTABLE PER FBPE'S.
 PLEASE ALSO CLARIFY BBC DESIGN ON
 TITLE BLOCK?? 61G15-23.002/ 61G1-16.004?
  
 8)NOTE: PLEASE SEE FBC 104.6.5, VALUE
 FOR SCOPE OF WORK NEEDS TO BE INCREASED
 DUE TO SCOPE PF WORK BEING PERFORMED.
 VALUE IS INCLUDE ALL LABOR AND MATERIALS
 PLEASE SEE BLDG REVIEW COMMENTS.
  
 9)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B) FOR PLANS REVIEWED FOR SAME COMMENTS
 IF PLANS COME BACK IN FOR 3RD REVIEW,
 AND ANY OF THE SAME COMMENTS FROM
 PREVIOUS TWO REVIEWS ARE NOT ADDRESSED
 A 4X FEE SHALL BE ISSUED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]