| 2004-04-28 00:00:00 | ********** UNSAT ********* |
| | |
| | PLEASE SEE SOME NOTES FORM FIRST REVIEW |
| | NOT DONE AND THERE ARE ALOS NEW NOTES. |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A SUBMITTED |
| | PANEL SCHEDULE. |
| | PANEL SCHEDULE MUST SHOWS CIRCUIT #'S, |
| | OCP, AWG ETC. |
| | |
| | 2)NOTE: PLEASE SEE NEC FOR DERATING |
| | OF INDIVIDUAL BRANCH CIRCUITS IN 1" |
| | SCH80 PVC CONDUIT. 240,TABLES ETC. |
| | |
| | 3)NOTE: PLEASE SHOW A/C EQUIPMENT ON |
| | ELECTRICAL PLANS ALONG WITH DISC AS |
| | REQ'D PER 440.11. |
| | |
| | 4)NOTE: PLEASE SHOW RECEPTS REQ'D UNDER |
| | 210.63 FOR A/C EQUIPMENT. |
| | |
| | 5)NOTE: PLEASE SEE BLDG USE IS BEING |
| | CHANGED FROM RESIDENCE TO COMM. |
| | PLEASE SEE TWO METER SYSTEM MUST BE |
| | REMOVED AND BE INSTALLED BACK TO SINLGE |
| | METER INSTALLATION. |
| | PLEASE ADJUST SERVICE ACCORD. |
| | |
| | 6)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/EXT LTS. |
| | |
| | 7)NOTE: PLEASE HAVE ENGINEER SIGN WITH |
| | COMPLETE "SIGNATURE" AS SHOWN ON LICENSE |
| | /RAISED SEAL AS REQ'D UNDER FS 471.025 |
| | INITIALS ARE NOT ACCEPTABLE PER FBPE'S. |
| | PLEASE ALSO CLARIFY BBC DESIGN ON |
| | TITLE BLOCK?? 61G15-23.002/ 61G1-16.004? |
| | |
| | 8)NOTE: PLEASE SEE FBC 104.6.5, VALUE |
| | FOR SCOPE OF WORK NEEDS TO BE INCREASED |
| | DUE TO SCOPE PF WORK BEING PERFORMED. |
| | VALUE IS INCLUDE ALL LABOR AND MATERIALS |
| | PLEASE SEE BLDG REVIEW COMMENTS. |
| | |
| | 9)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| | (B) FOR PLANS REVIEWED FOR SAME COMMENTS |
| | IF PLANS COME BACK IN FOR 3RD REVIEW, |
| | AND ANY OF THE SAME COMMENTS FROM |
| | PREVIOUS TWO REVIEWS ARE NOT ADDRESSED |
| | A 4X FEE SHALL BE ISSUED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |