| Plan Review Notes For Permit 04010010 |
| Permit Number |
04010010 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-06 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 2.INDICATE OUTSIDE AIR INTAKE, DUCT | | | SIZE, MATERIAL AND LAYOUT. | | | | | | 3.PLAN SHEET M-1 INDICATES 3 TON | | | SYSTEM, INDICATE IF THE EQUIPMENT IS | | | NEW OR EXISTING. | | | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 5.PLEASE NOTE THE LOCATION OF THE AHU | | | SHALL HAVE SUFFICIENT SPACE TO ALLOW FOR | | | INSPECTION, SERVICE, REPAIR OR REPLACE- | | | MENT.2001 FBC(M) 306.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|