2004-04-06 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL AND LAYOUT.
  
 3.PLAN SHEET M-1 INDICATES 3 TON
 SYSTEM, INDICATE IF THE EQUIPMENT IS
 NEW OR EXISTING.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 5.PLEASE NOTE THE LOCATION OF THE AHU
 SHALL HAVE SUFFICIENT SPACE TO ALLOW FOR
 INSPECTION, SERVICE, REPAIR OR REPLACE-
 MENT.2001 FBC(M) 306.1.
  