Plan Review Notes
Plan Review Notes For Permit 04010010
Permit Number 04010010
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-03-19 00:00:001) ACCORDING TO PERMIT APPLICATION, THE
 BUILDING WAS FORMERLY RESIDENTIAL AND
 IS BEING CHANGED TO BUSINESS. THIS
 CONVERSION WILL BE CLASSIFIED AS A
 CHANGE OF USE.
  
 2) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF 6" HIGH NUMBERS ARE REQUIRED.
  
 3) HANDRAILS REQUIRED ON BOTH SIDES
 OF ALL STAIRS AND RAMPS.
  
 4) NO EXIT SIGNS OR EMERGENCY LIGHTS
 SHOWN.
  
 5) NO INFORMATION PROVIDED WITH REGARDS
 TO PORTABLE FIRE EXTINGUISHERS.
  
 6) NO INFORMATION PROVIDED WITH REGARDS
 TO PORTABLE FIRE EXTINGUISERS.
  
 7) PLEASE PROVIDE INFORMATION ABOUT
 EXTERIOR DOOR LOCKS.
  
 8) DOOR LEADING FROM OFFICE TO EXTERIOR
 DOOR CANNOT BE SUBJECT TO LOCKING IF
 AN EXIT DOOR IS PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910