Plan Review Notes
Plan Review Notes For Permit 04010007
Permit Number 04010007
Review Stop B
Sequence Number 4
Notes
Date Text
2005-01-31 00:00:00DENIED
  
 1) THE TRUSS DRAWINGS THAT WERE
 SUBMITTED ARE FOR THE "B" ELEVATION AND
 THIS IS THE "A" ELEVATION.
  
 2) FBC 18O4.1.3 REQUIRES TO BOTTOM OF
 FOOTERS TO BR A MINIMUM OF 12" BELOW
 GRADE. CORRECT SHEET A16.
  
 3) THE SOFFIT NOTE ON A20 CALLS FOR
 STUCCO OVER 5/8" PLYWOOD. THIS IS THE
 NOTE FOR THE FRAME WALLS. PLYWOOD IS NOT
 INSTALLED BEHIND THE LATH ON THE
 SOFFITS.
  
 4) THE PRODUCT APPROVAL FOR THE SINGLE
 HUNG WINDOWS IS MISSING THE INSTALLATION
 DRAWINGS FOR CONCRETE OR MASONRY
 OPENINGS.
  
 5) THE PRODUCT APPROVALS FOR THE FIXED
 GLASS WINDOWS ARE NOT CORRECT. THE
 DRAWING NUMBERS ON PAGE ONE AND PAGE TWO
 DO NOT MATCH AND THE WINDOWS ARE NOT
 CURVED AT THE TOP.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714