| Plan Review Notes For Permit 04010007 |
| Permit Number |
04010007 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-01-31 00:00:00 | DENIED | | | | | | 1) THE TRUSS DRAWINGS THAT WERE | | | SUBMITTED ARE FOR THE "B" ELEVATION AND | | | THIS IS THE "A" ELEVATION. | | | | | | 2) FBC 18O4.1.3 REQUIRES TO BOTTOM OF | | | FOOTERS TO BR A MINIMUM OF 12" BELOW | | | GRADE. CORRECT SHEET A16. | | | | | | 3) THE SOFFIT NOTE ON A20 CALLS FOR | | | STUCCO OVER 5/8" PLYWOOD. THIS IS THE | | | NOTE FOR THE FRAME WALLS. PLYWOOD IS NOT | | | INSTALLED BEHIND THE LATH ON THE | | | SOFFITS. | | | | | | 4) THE PRODUCT APPROVAL FOR THE SINGLE | | | HUNG WINDOWS IS MISSING THE INSTALLATION | | | DRAWINGS FOR CONCRETE OR MASONRY | | | OPENINGS. | | | | | | 5) THE PRODUCT APPROVALS FOR THE FIXED | | | GLASS WINDOWS ARE NOT CORRECT. THE | | | DRAWING NUMBERS ON PAGE ONE AND PAGE TWO | | | DO NOT MATCH AND THE WINDOWS ARE NOT | | | CURVED AT THE TOP. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|