Plan Review Notes
Plan Review Notes For Permit 04010007
Permit Number 04010007
Review Stop B
Sequence Number 3
Notes
Date Text
2004-12-13 00:00:00DENIED
  
 1) THE ENERGY CALCULATIONS LIST THE
 CEILING INSULATION AS R-19 AND THE PLANS
 SPECIFY R-30. THE ENERGY CALCS. LIST
 EXTERIOR WOOD FRAME WALLS WITH R-11
 INSULATION AND THE PLANS SPECIFY 2X6
 WALL WITH R-19. PLEASE CORRECT.
  
 2) FAC 61G15-23.002 REQUIRES THE
 ORIGINAL WET SIGNATURE OF THE TRUSS
 ENGINEER TO BE ON THE TRUSS LAYOUT PLANS
 AND DRAWINGS.
  
 3) THE CEMENTITIOUS FINISH ON THE SOFFIT
 IS REQUIRED TO BE 5/8" THICK PER FBC
 25O4.2.1 AND ASTM C 926.
  
 4) SUBMIT PRODUCT APPROVALS AND SPECS.
 FOR THE ONE HOUR FIRE RATED GLASS
 BLOCK.
  
 5) SUBMIT THE EVALUATION REPORT FOR THE
 STRUCTURAL MULLIONS LISTING THE DESIGN
 PRESSURES.
  
 6) SUBMIT THE INSTALLATION DRAWINGS AND
 DESIGN PRESSURES FOR THE SINGLE HUNG
 WINDOWS.
  
 7) SUBMIT THE PRODUCT APPROVALS FOR THE
 FIXED GLASS WINDOWS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714