| Plan Review Notes For Permit 04010007 |
| Permit Number |
04010007 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-12-13 00:00:00 | DENIED | | | | | | 1) THE ENERGY CALCULATIONS LIST THE | | | CEILING INSULATION AS R-19 AND THE PLANS | | | SPECIFY R-30. THE ENERGY CALCS. LIST | | | EXTERIOR WOOD FRAME WALLS WITH R-11 | | | INSULATION AND THE PLANS SPECIFY 2X6 | | | WALL WITH R-19. PLEASE CORRECT. | | | | | | 2) FAC 61G15-23.002 REQUIRES THE | | | ORIGINAL WET SIGNATURE OF THE TRUSS | | | ENGINEER TO BE ON THE TRUSS LAYOUT PLANS | | | AND DRAWINGS. | | | | | | 3) THE CEMENTITIOUS FINISH ON THE SOFFIT | | | IS REQUIRED TO BE 5/8" THICK PER FBC | | | 25O4.2.1 AND ASTM C 926. | | | | | | 4) SUBMIT PRODUCT APPROVALS AND SPECS. | | | FOR THE ONE HOUR FIRE RATED GLASS | | | BLOCK. | | | | | | 5) SUBMIT THE EVALUATION REPORT FOR THE | | | STRUCTURAL MULLIONS LISTING THE DESIGN | | | PRESSURES. | | | | | | 6) SUBMIT THE INSTALLATION DRAWINGS AND | | | DESIGN PRESSURES FOR THE SINGLE HUNG | | | WINDOWS. | | | | | | 7) SUBMIT THE PRODUCT APPROVALS FOR THE | | | FIXED GLASS WINDOWS. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|