| Plan Review Notes For Permit 04010007 |
| Permit Number |
04010007 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-10-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT P-3 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. - ALSO SEE | | | SHT P-1 FLOOR PLAN, (B UNIT LEFT)AND | | | SHT P-2 FLOOR PLAN, (A UNIT LEFT) SANT. | | | LAYOUT. | | | A) WATER CLOSET IS NOT VENTED PER SECT- | | | ION 908.3 (B UNIT) | | | B) TWO SANITARY LINES ARE SHOWN FOR THE | | | LAVS. (A UNIT) | | | 2) SHTS P-2, & P-3 REQUIRE A CERTIFICATE | | | OF AUTHORIZATION AS "ENGINEERS" IMPLIES | | | A PARTNERSHIP. FS 481.219 & FAC 61G1-16. | | | 003. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|