2004-10-14 00:00:00"MASTER" 6 UNIT/2 STORY
  
 DENIED
  
 1)REDLINE CHANGES INITIALED AND DATED BY
 THE DESIGNER OF RECORD ARE NOT ALLOWED
 ON A "MASTER" PLAN. REVISE SHEET A-15
 WHICH HAS BEEN REDLINED BY D.O.R.
  
 2) REVISE THE PLYWOOD SHEATHING NAILING
 SCHEDULE ON S-4 TO CLARIFY THAT THE 8D
 RING SHANK NAILS ARE REQUIRED FOR THE
 ROOF SHEATHING IN ZONE 3 ONLY.
  
 3) REVISE NOTE #7 ON S2 TO 8F8-1B, NOT
 8FB-1B.
  
 4) REVISE THE NOTE FOR THE DOORS IN THE
 GARAGE DEMISING WALLS TO SAY 3/4 HOUR
 FIRE RATED DOORS, ON SHEETS A-1, A-3,
 A-4 AND A7.
  
 5) SPECIFY THE EMBED DEPTH OF THE 3/4"
 DIA. ANCHOR BOLTS FOR THE STEEL COLUMN
 BASES IN NOTE 6 ON S-1.
  
 6) SECTION 8 ON S-6 IS INCORRECTLY
 SPECIFIED ON SHEET S-3 FOR THE WALL
 BETWEEN UNITS #3L AND 3R. THE TRUSSES
 ARE PARALLEL TO THE WALL AT THIS
 LOCATION. PLEASE CORRECT.
  
 7) THE TRUSS LAYOUT AND DRAWINGS SHOW A
 2 MEMBER GRO3 ROOF TRUSS PARALLEL TO THE
 THE WALL BETWEEN UNITS #3L AND 3R. THIS
 TRUSS HAS A TOP CORD THAT IS FLAT. THIS
 IS NOT INDICATED ON THE PLANS AND NO
 CONNECTORS ARE SPECIFIED. SEE SECTION 1
 ON S-6. PLEASE REVIEW AND MAKE THE
 NECESSARY CORRECTIONS.
  
 8)REVISE THE UPLIFT VALUE OF THE SIMPSON
 HETAL 20 CONNECTOR IN THE SCHEDULE ON
 S-3 TO 1810#, WHICH IS THE VALUE IN THE
 2004 SIMPSON CATALOG TABLE ON PAGE 127,
 WHICH INCLUDES THE LOAD DURATION
 INCREASE ATTRIBUTED TO THE PROPETIES OF
 WOOD BUT NOT THE STRESS INCREASE ON THE
 STEEL CAPACITY, WHICH IS NOT ALLOWED BY
 THE FLORIDA BUILDING CODE. SEE ATTACHED.
  
 9) PLEASE GATHER ALL PRODUCT APPROVALS
 FROM PREVIOUS SUBMITTALS AND COMBINE
 WITH THE NEW SUBMITTALS TO MAKE 3
 COMPLETE SETS OF PLANS AND PRODUCT
 APPROVALS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714