Plan Review Notes
Plan Review Notes For Permit 04010007
Permit Number 04010007
Review Stop M
Sequence Number 1
Notes
Date Text
2004-01-22 00:00:00DENIED:
 1.PLANS ARE NOT SIGNED SEALED AND
 DATED BY THE ENGINEER AS REQUIRED BY FS
 471.025 & THE FAC 61G15-23.002.
  
 2.PLAN SHEET A-17 & DETAIL 2 ON PLAN
 SHEET A-21 INDICATE A 1 HOUR FIRE RATED
 FLOOR/CEILING ASSEMBLY.UNITS 2R, 3R,
 3L, 2L GRILLES TERMINATING AT THE
 CEILING SHALL HAVE PROTECTION.
 DUCTWORK PENTRATING RATED ASSEMBLY TO
 THE SECOND FLOOR SHALL BE PROTECTED BY
 MEANS OF A FIRE DAMPER OR "RATED SHAFT"
 ASSEMBLY.PLEASE REIVSE PLANS TO
 INCLUDE DETAILS FOR THESE TYPE OF
 PENTRATIONS.
  
 3.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 4.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL AND LAYOUT.
  
 5.RETURN AIR JUMPER ARE NOT SIZED
 PROPERLY.MASTER BEDROOMS ARE TO
 INCLUDE ALL SUPPLY AIR TO THE MASTER
 SUITE (CLOSETS, BATHROOM, ETC).PLEASE
 SEE THE ATTACHED SCHEDULE FOR PROPER
 SIZING OF RETURN AIR.
  
 6.ENERGY AND MANUAL J CALCULATIONS
 REQUIRED FOR APPROVAL PER 2001 FBC
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.