| 2004-01-22 00:00:00 | DENIED: |
| | 1.PLANS ARE NOT SIGNED SEALED AND |
| | DATED BY THE ENGINEER AS REQUIRED BY FS |
| | 471.025 & THE FAC 61G15-23.002. |
| | |
| | 2.PLAN SHEET A-17 & DETAIL 2 ON PLAN |
| | SHEET A-21 INDICATE A 1 HOUR FIRE RATED |
| | FLOOR/CEILING ASSEMBLY.UNITS 2R, 3R, |
| | 3L, 2L GRILLES TERMINATING AT THE |
| | CEILING SHALL HAVE PROTECTION. |
| | DUCTWORK PENTRATING RATED ASSEMBLY TO |
| | THE SECOND FLOOR SHALL BE PROTECTED BY |
| | MEANS OF A FIRE DAMPER OR "RATED SHAFT" |
| | ASSEMBLY.PLEASE REIVSE PLANS TO |
| | INCLUDE DETAILS FOR THESE TYPE OF |
| | PENTRATIONS. |
| | |
| | 3.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2001 FBC(M) 403.3. |
| | |
| | 4.INDICATE OUTSIDE AIR INTAKE, DUCT |
| | SIZE, MATERIAL AND LAYOUT. |
| | |
| | 5.RETURN AIR JUMPER ARE NOT SIZED |
| | PROPERLY.MASTER BEDROOMS ARE TO |
| | INCLUDE ALL SUPPLY AIR TO THE MASTER |
| | SUITE (CLOSETS, BATHROOM, ETC).PLEASE |
| | SEE THE ATTACHED SCHEDULE FOR PROPER |
| | SIZING OF RETURN AIR. |
| | |
| | 6.ENERGY AND MANUAL J CALCULATIONS |
| | REQUIRED FOR APPROVAL PER 2001 FBC |
| | CHAPTER 13. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |