Plan Review Notes
Plan Review Notes For Permit 04010007
Permit Number 04010007
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-01-08 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES ARE REQUIRED.
 COULD NOT LOCATE THEM ON ELEVATION
 DRAWINGS.
  
 3) ENTRY DOORS SHOULD BE AT LEAST
 20 MINUTE FIRE RATED.
  
 4) PLEASE VERIFY IF ONE HOUR TENANT
 DEMISING WALLS WILL BE ACCEPTED BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ONE HOUR WALLS ARE ALLOWED IN APARTMENTS
 BUT TOWNHOMES USUALLY REQUIRE TWO
 HOUR DEMISING WALLS. ARE THESE UNITS
 RENTALS OR ARE THEY GOING TO BE SOLD
 AND BE FEE SIMPLE. PLEASE ADVISE.
  
 5) ANY AND ALL THREE STORY BUILDINGS
 IN THE DEVOLPMENT WILL REQUIRE FIRE
 SPRINKLER PROTECTION.
  
 6) IF SECURITY GATES ARE PROVIDED,
 TWENTY FEET IN CLEAR WIDTH WILL BE
 REQUIRED FOR FIRE RESCUE ACCESS. A
 KNOX-BOX KEY SWITCH WILL BE REQUIRED.
  
 7) COULD NOT LOCATE FIRE EXTINGUISHERS.
 PLEASE ADVISE LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910