2004-01-12 00:00:00*********** UNSAT ******************
  
 1)NOTE: PLANS REFERENCE 1999 NEC.
 WE ARE UNDER THE 2002 NEC
 7/1/2003
  
 2)NOTE: PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 3)NOTE: PLEASE PROVIDE ALL LICENSE #`'S
 ON TITLE BLOCK(S) AS REQ'D UNDER FAC
 61G15-23.002 / FS 471.023
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5))NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
  
 6) NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 7)) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52EREAR
  
 8)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 EMT AS BEING DIRECT BURIAL FOR FEEDERS.
 PLEASE SEE THIS IS NOT PERMITTED UNDER
 LOCAL AMENDMENTS 348-5.
 ALSO SEE 358 NEC
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY AFFECT ELECTRICAL PLANS.
 PLEASE ALSO NOTE: INFORMATION REQ'D ON
 TITLE BLOCKS FOR ARCHS/ENGS ARE REQ'D
 OF ALL TRADES AND ALL SHEETS, WEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEW-
 -ERS.
  
 9)NOTE: PLEASE LIST/SHOW ALL HEIGHTS
 UNDER FHAR CFR 100.205.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  