2004-01-22 00:00:00DENIED:
 1.PLANS ARE NOT SIGNED, SEALED, AND
 DATED BY THE ENGINEER AS REQUIRED BY FS
 471.025 & THE FAC 61G15-23.002.
  
 2.PLAN SHEET A-9 & A-13.1 DETAIL 1 &
 2, INDICATE 1 HOUR FIRE RATED
 FLOOR/CEILING & CEILING/ROOF
 ASSEMBLIES.PENETRATIONS THROUGH RATED
 ASSEMBLIES SHALL COMPY WITH 2001 FBC(M)
 607.2.
  
 3.DUCTS PENETRATING MORE THAN ONE
 STORY SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE PER 2001 FBC(M) 607.4.
 PLEASE PROVIDE DETAIL OF SHAFT
 ENCLOSURE.
  
 4.PLEASE INDICATE PROTECTION OF
 EXHAUST DUCT WORK PENETRATING 1 HOUR
 CEILING/ROOF ASSEMBLY. (PLAN SHEET M-2)
  
 5.PLAN SHEET RETURN AIR JUMPERS ARE
 NOT SIZED PROPERLY.PLEASE NOTE,
 MASTER BEDROOM IS TO INCLUDE ALL AIR TO
 THE MASTER SUITE PER 2001 FBC(M) 601.4
 EXCEPTION 1 AND 4 (SEE THE ATTACHED
 SCHEDULE FOR PROPER SIZING).
  
 6.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 7.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL, AND LAYOUT.
  
 8.ENERGY AND MANUAL J CALCULATIONS
 REQUIRED FOR APPROVAL PER 2001 FBC
 CHAPTER 13.
  