| 2004-01-22 00:00:00 | DENIED: |
| | 1.PLANS ARE NOT SIGNED, SEALED, AND |
| | DATED BY THE ENGINEER AS REQUIRED BY FS |
| | 471.025 & THE FAC 61G15-23.002. |
| | |
| | 2.PLAN SHEET A-9 & A-13.1 DETAIL 1 & |
| | 2, INDICATE 1 HOUR FIRE RATED |
| | FLOOR/CEILING & CEILING/ROOF |
| | ASSEMBLIES.PENETRATIONS THROUGH RATED |
| | ASSEMBLIES SHALL COMPY WITH 2001 FBC(M) |
| | 607.2. |
| | |
| | 3.DUCTS PENETRATING MORE THAN ONE |
| | STORY SHALL BE PROTECTED BY A SHAFT |
| | ENCLOSURE PER 2001 FBC(M) 607.4. |
| | PLEASE PROVIDE DETAIL OF SHAFT |
| | ENCLOSURE. |
| | |
| | 4.PLEASE INDICATE PROTECTION OF |
| | EXHAUST DUCT WORK PENETRATING 1 HOUR |
| | CEILING/ROOF ASSEMBLY. (PLAN SHEET M-2) |
| | |
| | 5.PLAN SHEET RETURN AIR JUMPERS ARE |
| | NOT SIZED PROPERLY.PLEASE NOTE, |
| | MASTER BEDROOM IS TO INCLUDE ALL AIR TO |
| | THE MASTER SUITE PER 2001 FBC(M) 601.4 |
| | EXCEPTION 1 AND 4 (SEE THE ATTACHED |
| | SCHEDULE FOR PROPER SIZING). |
| | |
| | 6.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2001 FBC(M) 403.3. |
| | |
| | 7.INDICATE OUTSIDE AIR INTAKE, DUCT |
| | SIZE, MATERIAL, AND LAYOUT. |
| | |
| | 8.ENERGY AND MANUAL J CALCULATIONS |
| | REQUIRED FOR APPROVAL PER 2001 FBC |
| | CHAPTER 13. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |