2004-01-12 00:00:00************* UNSAT *****************
  
 1)NOTE: PLANS REFERENCE THE 1999 NEC,
 PLEASE SEE THAT WE ARE UNDER THE 2002
 NEC.
  
 2)NOTE: PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 3 )NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5) NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 6)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 AS REQ'D UNDER FAC 61G15-23.002/FS 471
 PLEASE ALSO SEE FS 471.023
  
 7)NOTE: PLEASE SEE RISER, SHOWS EMT
 BEING INSTALLED FOR DIRECT BURIAL.
 PLEASE SEE THAT THIS IS NOT PERMITTED.
 SEE 348-5 LOCAL AMENDMENTS.
 PLEASE ALSO SEE NEC 358
  
 8)NOTE: PLEASE SEE FHAR CFR 100.205
 FOR ALL HEIGHT REQ'MENTS. PLEASE SHOW
 ON PLANS.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR UNIT MAINS, BUT NOT FOR 1200A
 MAIN.
  
 10) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52EREAR?
  
 11)NOTE:PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]