| Date |
Text |
| 2004-02-11 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04010006 (8 UNIT) |
| | ADD: 1100 N CONGRESS |
| | CONT: WCI N CONGRESS |
| | CONTACT PERSON: DOUG BERK |
| | TEL: (561)262-3684 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ARCH: WCI ARCHITECTURE & LAND PLANNING |
| | CONTACT: PETER SYNOYANNIS |
| | (954) 575-4200 |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | THE COMMENTS FROM 04010005 (4) UNIT |
| | BUILDING ARE APPLICIABLE ACCEPT FOR THE |
| | FAIR HOUSING. |
| | |
| | 1)903.8.2 FLOR ST STATUTE 553.895(2) |
| | ALL RESIDENTIAL BUILD. 3 OR MORE STORIES |
| | TALL WHETHER DESIGNATED AS TOWNHOUSE, |
| | CONDOMINIUMS, "APARTMENT HOUSES, |
| | TENEMENTS, GARDEN APARTMENTS OR BY ANY |
| | OTHER NAME SHALL BE SUPPLIED BY FIRE |
| | SPRINKLERS MEETING NFPA 101. |
| | PROVIDE 3 COPIES OF FIRE SPRINKLER |
| | PLANS TO BE INCLUDED WITH THE BUILDING |
| | PLANS. |
| | |
| | 2) PROVIDE THE MEAN ROOF HEIGHT OF THE |
| | BUILDING FROM "GRADE" TO INCLUDE 1/2 THE |
| | HEIGHT OF THE TRUSSES OFF OF THE HEIGH- |
| | EST BEAM. APPROX- 38'-4 1/2". |
| | |
| | 3) SHEET S-4 TRUSS PLAN DOES NOT INDI- |
| | CATE THE TRUSS OR GIRDER LOADS, VERTICAL |
| | HORIZONTAL AND GRAVITY LOADS TO BE |
| | RESISTED. THE TRUSS ANCHOR LEGOND |
| | "E-H" DOES NOT GIVE ANY VALUE FOR THE |
| | FASTENER!!!!!!!!!!!!!!!!!!!!!!!!!!!! |
| | |
| | 4) SHEET S-3 INDICATES PRECAST LINTELS |
| | ARETO BE USED, PROVIDE LINTEL SCHEDULE |
| | AND ALLOWABLE LOADS VS SPANS. |
| | |
| | 5) SHEET S-5 WALL AND ROOF PRESSURE |
| | ZONES INDICATE LOW PRESSURES! SINCE THE |
| | MEAN ROOF HEIGHT IS > 35' A HEIGHT |
| | ADJUSTMENT FACTOR IS REQUIRED OF 1.09 |
| | SEE TABLE 1606.2D. |
| | |
| | 6) SHEET S-5 ROOF NAILING SCHEDULE |
| | ZONE# 3 NAILS ARE TO BE "RING SHANK". |
| | WEST PALM BEACH AMENDMENT TABLE 2306.1. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |