Plan Review Notes
Plan Review Notes For Permit 04010005
Permit Number 04010005
Review Stop B
Sequence Number 4
Notes
Date Text
2004-12-03 00:00:00BUILDING REVISION DENIED
  
 1) SECTION 3 ON A11 THE INSULATION ABOVE
 THE GARAGE HAS BEEN DELETED WHICH
 COMPROMISES THE BUILDING ENVELOPE
 INSULATION.
  
 2) FBC 2504.2.1 AND ASTM C 926 REQUIRE A
 HORIZONTAL APPICATION OF STUCCO OVER
 METAL PLASTER BASE TO BE A MINIMUM OF
 5/8" THICK.SEE SECTIONS ON A11 AND A13.
  
 3) FBC 1804.1.3 REQUIRES THE BOTTOM OF
 FOOTINGS TO BE A MINIMUM OF 12" BELOW
 GRADE. REVISE WALL SECTIONS ON A11 AND
 A12.
  
 4) ASTM C 926 REQUIRES STUCCO OVER METAL
 PLASTER BASE OVER A SOLID BASE APPLIED
 ON VERTICAL TO BE 7/8" THICK. REVISE
 DETAILS 1 AND 2 ON A20.
  
 5) THE GARAGE DOOR BUCK DETAIL 2 ON A19
 WAS DELETED. PROVIDE A BUCK ATTACHMENT
 DETAIL FOR THE OVERHEAD GARAGE DOOR.
  
 6) DETAIL 3 ON A19 SPECIFIES A COUNTY
 BUILDING CODE. PLEASE REMOVE THIS
 REFRENCE AS THERE IS NOT ONE.
  
 7) THE CITY OF WEST PALM BEACH
 AMENDMENTS TO FBC TABLE 2306.1 REQUIRES
 ROOF SHEATHING TO BE NAILED WITH 8D
 COMMONS AT 6"OC AT EDGES AND
 INTERMEDIATE IN ZONES 1 AND 2. BUILDINGS
 WITH A MEAN ROOF HEIGHT OF 25'-35'
 REQUIRES 8D RING SHANK NAILS 4"OC AT
 EDGES AND 6"OC INTERMEDIATE. REVISE
 SCHEDULE ON S3.
  
 8) SEVERAL ITEMS HAVE BEEN CHANGED ON
 THE PLANS THAT WERE NOT CLOUDED AND
 NUMBERED. FOR EXAMPLE DETAIL 14 ON S5,
 PA23 STRAPS ON FLOOR JOISTS, BATHROOM
 DOOR SIZES, DOOR SWING AT GARAGE, ETC.
 IT HELPS TO EXPEDITE PLAN REVIEW WHEN
 ALL REVISED ITEMS ARE SPECIFIED.
  