| Plan Review Notes For Permit 04010005 |
| Permit Number |
04010005 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-08-11 00:00:00 | PLANS SUBMITTED ARE APPROVED.MANUAL J | | | CALCULATIONS INDICATE TOTAL COOLING LOAD | | | CALCUALTION AS 27,323 BTUH THE ENERGY | | | CALCS INDICATE 62,000 BTU/HR.ENERGY | | | CALCULATIONS ALSO INDICATE A CREDIT FOR | | | CROSS VENTILATION.CROSS VENTILATION | | | CREDIT SHALL COMPLY WITH 2001 FBC | | | CHAPTER 13 SUB-CHAPTER 607.1.A.3.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|