| Date |
Text |
| 2004-01-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMIN. CODE |
| | FLORIDA STATUTES |
| | |
| | 1) INDICATE SPECIFICATION "A" OR "B" AS |
| | REQUIRED IN FHA DESIGN MANUAL REQUIRE- |
| | MENT 7B PAGES 7.34 & 7.35. |
| | 2) SHOW LAV HEIGHT PER FHA DESIGN MANUAL |
| | PAGE 9512 SECTION "V". |
| | 3) SHT A-15 GRAP BAR BLOCKING DETAILS |
| | SHALL REFLECT BACKING IN CHAPTER 6 OF |
| | THE FHA DESIGN MANUAL. |
| | 4) A SANITARY AND A WATER RISER DIAGRAM |
| | ARE REQUIRED PER SECTION 104.3.1.1 |
| | 5) SHT P-1 CLEANOUT IN UNIT #3 NOT RE- |
| | QUIRED AND IS NOT ACCESSIBLE. |
| | 6) SHT P-1 SANITARY PIPING IS FAINT AND |
| | UNREADABLE. SUBMIT INFORMATION WITH |
| | CLAIRITY. 104.2.1 |
| | 7) SHT P-1 CLEANOUT REQUIRED NEAR THE |
| | JUNCTION OF BLDG DRAIN AND BLDG SEWER & |
| | CAN BE A TWO WAY C/O. SECTION 708.3.5 |
| | 8) PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) & FS 471 |
| | |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |