2004-01-29 00:00:00DENIED:
 1.PLANS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE ENGINEER PER
 FS 471.025 & THE FAC 61G15-23.002.
  
 2.PROVIDE ADDITIONAL INFORMATION ON
 THE CEILING/FLOOR & CEILING/ROOF
 ASSEMBLIES.ARE THESE FIRE RATED
 ASSEMBLIES?PLEASE PROVIDE DETAIL & UL
 ASSEMBLY LISTING.
  
 3.PLAN SHEET M-1 UNIT A INDICATES A
 RETURN AIR DUCT PENETRATING THE FIRE
 RATED WALL AT THE GARAGE.FIRE DAMPER
 REQUIRED WHERE DUCTS PENETRATE FIRE
 RATED WALLS OR CEILING/FLOOR ASSEMBLIES.
  
 4.PLAN SHEET M-1, RETURN AIR JUMPERS
 ARE NOT SIZED PROPERLY. SEE THE ATTACHED
 SCHEDULE FOR PROPER SIZING PER 2001
 FBC(M) 601.4 EXCEPTIONS 1 THROUGH 3.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
 PLEASE NOTE THE ONLY BUILDINGS EXEMPT
 FROM PROVIDING OUTSIDE AIR ARE R-3, ONE
 AND TWO FAMILY DWELLINGS.
  
 6.INDICATE OUTSIDE AIR DUCT SIZE,
 MATERIAL, LAYOUT AND INTAKE ON PLAN.
  
 7.ENERGY AND MANUAL J CALCULATIONS
 REQUIRED FOR APPROVAL PER 2001 FBC
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.