| 2004-01-29 00:00:00 | DENIED: |
| | 1.PLANS ARE REQUIRED TO BE SIGNED, |
| | SEALED AND DATED BY THE ENGINEER PER |
| | FS 471.025 & THE FAC 61G15-23.002. |
| | |
| | 2.PROVIDE ADDITIONAL INFORMATION ON |
| | THE CEILING/FLOOR & CEILING/ROOF |
| | ASSEMBLIES.ARE THESE FIRE RATED |
| | ASSEMBLIES?PLEASE PROVIDE DETAIL & UL |
| | ASSEMBLY LISTING. |
| | |
| | 3.PLAN SHEET M-1 UNIT A INDICATES A |
| | RETURN AIR DUCT PENETRATING THE FIRE |
| | RATED WALL AT THE GARAGE.FIRE DAMPER |
| | REQUIRED WHERE DUCTS PENETRATE FIRE |
| | RATED WALLS OR CEILING/FLOOR ASSEMBLIES. |
| | |
| | 4.PLAN SHEET M-1, RETURN AIR JUMPERS |
| | ARE NOT SIZED PROPERLY. SEE THE ATTACHED |
| | SCHEDULE FOR PROPER SIZING PER 2001 |
| | FBC(M) 601.4 EXCEPTIONS 1 THROUGH 3. |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2001 FBC(M) 403.3. |
| | PLEASE NOTE THE ONLY BUILDINGS EXEMPT |
| | FROM PROVIDING OUTSIDE AIR ARE R-3, ONE |
| | AND TWO FAMILY DWELLINGS. |
| | |
| | 6.INDICATE OUTSIDE AIR DUCT SIZE, |
| | MATERIAL, LAYOUT AND INTAKE ON PLAN. |
| | |
| | 7.ENERGY AND MANUAL J CALCULATIONS |
| | REQUIRED FOR APPROVAL PER 2001 FBC |
| | CHAPTER 13. |
| | |