| 2004-01-08 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | | | 2) BUILDING ADDRESSES ARE REQUIRED. | | | COULD NOT LOCATE THEM ON ELEVATION | | | DRAWINGS. | | | | | | 3) ENTRY DOORS SHOULD BE AT LEAST | | | 20 MINUTE FIRE RATED. | | | | | | 4) PLEASE VERIFY IF ONE HOUR TENANT | | | DEMISING WALLS WILL BE ACCEPTED BY | | | THE CONSTRUCTION SERVICES DEPARTMENT. | | | ONE HOUR WALLS ARE ALLOWED IN APARTMENTS | | | BUT TOWNHOMES USUALLY REQUIRE TWO | | | HOUR TENANT DEMISING WALLS. ARE THESE | | | UNITS RENTALS OR ARE THEY GOING TO BE | | | SOLD AND BE FEE SIMPLE. PLEASE ADVISE. | | | | | | 5) ANY AND ALL THREE STORY BUILDINGS | | | IN THE DEVELOPMENT WILL REQUIRE FIRE | | | SPRINKLER PROTECTION. | | | | | | 6) IF SECURITY GATES ARE PROVIDED, | | | TWENTY FEET IN CLEAR WIDTH WILL BE | | | REQUIRED FOR FIRE RESCUE ACCESS. A | | | KNOX-BOX KEY SWITCH WILL BE REQUIRED. | | | | | | 7) COULD NOT LOCATE FIRE EXTINGUISHERS. | | | PLEASE ADVISE LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|