Plan Review Notes
Plan Review Notes For Permit 04010005
Permit Number 04010005
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-12 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY ENGINEER OF RECORD.
 PLEASE SEE MISSING LICENSE INFORMATION
 AS REQ'D UNDER FAC 61G15-23.002/ FS 471.
 .025.
 PLEASE ALSO SEE FS 471.023(IF APPLICABLE
  
 2)NOTE: PLEASE LIST THE REQ'D DEDICATED
 BATH(S) CIRCUIT(S) PER 210.52D/210.11C3
  
 3)NOTE: PLEASE SEE PLANS SHOWS "J" BOX
 AT LOCATION WHERE A MIN LT FIXTURE
 MAY BE REQ'D UNDER LS 101 5-8. PLEASE
 ALSO SEE 210.70
  
 4)NOTE: PLEASE SEE RISER, SHOWS FEEDER
 CONDUIT IN PVC OR EMT, PLEASE SEE THAT
 EMT IS NOT PERMITTED FOR DIRECT BURIAL.
 THIS IS ALSO NOT PERMITTED UNDER LOCAL
 AMENDMENTS.
  
 5)NOTE: PLEASE CLARIFY COLD WATER AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
  
  
 6)NOTE: PLEASE LIST THE REQ'D HEIGHTS
 PER FHAR 24CFR100.205
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 PLEASE SEE PLANS REFERENCE THE 1999 NEC
 WE ARE UNDER THE 2002 NEC.