| 2004-02-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMIN. CODE |
| | FLORIDA STATUTES |
| | |
| | COMMENTS FROM PREVIOUS REVIEW WILL NEED |
| | TO BE ADDRESSED PROPERLY. THE COMMENT |
| | NUMBER FROM PREVIOUS WILL REMAIN THE |
| | SAME FOR CLAIRITY. |
| | 2) SHT A01.1 SHOW CLEAR FLOOR SPACE FOR |
| | LAV'S AND W/C'S IN TOILET ROOMS PER SEC |
| | 11-4.22.3. DOOR SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY FIX- |
| | TURE. SEC 11-4.22.2 |
| | 5) SHT P-2 PROVIDE STRUCTURAL INFORMAT- |
| | ION FOR BACKING, FASTENERS, ECT FOR THE |
| | WATER HEATER SHELF. - RESPONSE INDICATES |
| | THE SHELF WILL BE FASTENED TO THE WALL |
| | WITH 4 - 1/4" DIA STEEL FASTENERS. - |
| | INDICATE IF THIS WILL BE A SOLID WALL OR |
| | IF BACKING WILL BE USED. IF BACKING |
| | SPECIFY TYPE AND WIDTH BEING USED. ALSO |
| | SPECIFY TYPE AND LENGTH OF FASTENERS. |
| | 7) PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) - PER FBPE |
| | RULING, INITIALS ARE NOT ACCEPTABLE, AND |
| | A SIGNATURE IS REQUIRED ON SEAL. - RES- |
| | PONSE NOTED, BUT INITIALS ARE STILL BE- |
| | ING USED ON SEAL. A MINIMUM OF FIRST AND |
| | LAST NAME AS SHOWN ON LICENSE IS REQUIR- |
| | ED. |
| | *****************NEW COMMENT************ |
| | 1B) SHT P-2 WATER RISER DIAGRAM, THE |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | NOTE: WATER HAMMER ARRESTORS ARE ONLY |
| | REQUIRED AT QUICK CLOSING VALVES SUCH AS |
| | DISHWASHERS, WASH MACHINES, AND ICE |
| | MAKERS PER SECTION 604.9. |
| | |
| | REVIEW BY KEN STEVENS |