2004-02-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEW WILL NEED
 TO BE ADDRESSED PROPERLY. THE COMMENT
 NUMBER FROM PREVIOUS WILL REMAIN THE
 SAME FOR CLAIRITY.
 2) SHT A01.1 SHOW CLEAR FLOOR SPACE FOR
 LAV'S AND W/C'S IN TOILET ROOMS PER SEC
 11-4.22.3. DOOR SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIX-
 TURE. SEC 11-4.22.2
 5) SHT P-2 PROVIDE STRUCTURAL INFORMAT-
 ION FOR BACKING, FASTENERS, ECT FOR THE
 WATER HEATER SHELF. - RESPONSE INDICATES
 THE SHELF WILL BE FASTENED TO THE WALL
 WITH 4 - 1/4" DIA STEEL FASTENERS. -
 INDICATE IF THIS WILL BE A SOLID WALL OR
 IF BACKING WILL BE USED. IF BACKING
 SPECIFY TYPE AND WIDTH BEING USED. ALSO
 SPECIFY TYPE AND LENGTH OF FASTENERS.
 7) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - PER FBPE
 RULING, INITIALS ARE NOT ACCEPTABLE, AND
 A SIGNATURE IS REQUIRED ON SEAL. - RES-
 PONSE NOTED, BUT INITIALS ARE STILL BE-
 ING USED ON SEAL. A MINIMUM OF FIRST AND
 LAST NAME AS SHOWN ON LICENSE IS REQUIR-
 ED.
 *****************NEW COMMENT************
 1B) SHT P-2 WATER RISER DIAGRAM, THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 NOTE: WATER HAMMER ARRESTORS ARE ONLY
 REQUIRED AT QUICK CLOSING VALVES SUCH AS
 DISHWASHERS, WASH MACHINES, AND ICE
 MAKERS PER SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]