Date Text
2004-03-08 00:00:00*** REDLINED**
 NO EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO FIRST MEANS OF DISCONNECT.
 250.24.
 EG, IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISC.
  
  
 ELECTRICAL PLANS STAMPED.