| Plan Review Notes For Permit 03121694 |
| Permit Number |
03121694 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-08 00:00:00 | *** REDLINED** | | | NO EQUIPMENT GROUNDING CONDUCTOR FROM | | | METER TO FIRST MEANS OF DISCONNECT. | | | 250.24. | | | EG, IS ONLY INSTALLED AFTER THE FIRST | | | MEANS OF DISC. | | | | | | | | | ELECTRICAL PLANS STAMPED. |
|