| 2004-01-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMIN. CODE |
| | FLORIDA STATUTES |
| | CITY CODE |
| | |
| | 1) SUBMIT A DETAIL FOR THE BREAKROOM |
| | SINK SHOWING COMPLIANCE WITH SECTION |
| | 11-4.24 AND ALL SUBSECTIONS. |
| | 2) SHT A01.1 SHOW CLEAR FLOOR SPACE FOR |
| | LAV'S AND W/C'S IN TOILET ROOMS PER |
| | SECTION 11-4.22.3. DOOR SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| | ANY FIXTURE. 11-4.22.2 |
| | 3) SHT P-1 CONDENSATE SHALL NOT DRAIN |
| | INTO THE SANITARY SYSTEM. CONDENSATE |
| | SHALL DRAIN TO THE OUTSIDE OF THE BLDG. |
| | AND TIE INTO A STORM LINE, CATCH BASIN, |
| | OR DRYWELL. CITY CODE SECTION 90-203. |
| | 4) SHTS P-1 & P-2 ELECTRIC WATER HEATER |
| | AND DETAIL, THERMAL EXPANSION CONTROL IS |
| | REQUIRED PER SECTION 607.3.2. |
| | 5) SHT P-2 PROVIDE STRUCTURAL INFORMAT- |
| | ION FOR BACKING, FASTENERS, ECT FOR THE |
| | WATER HEATER SHELF. |
| | 6) SHT P-2 SUBMIT THE WATER RISER DIA- |
| | GRAM IN AN ISOMETRIC FORM. SECTION |
| | 103.1.1. |
| | 7) PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) - PER FBPE |
| | RULING, INITIALS ARE NOT ACCEPTABLE, AND |
| | A SIGNATURE IS REQUIRED ON SEAL. |
| | |