2004-01-26 00:00:00PROVISO:
 PLAN SHEET M-2 A/C EQUIPMENT SCHEDULE
 NOTE #3 "SMOKE DETECTOR MOUNTED ON
 RETURN", PER 2001 FBC(M) 606.2.1 DUCT
 SMOKE DETECTORS TO INSTALLED ON THE
 SUPPLY AIR NOT THE RETURN.
  
 PLEASE CLARIFY THE FIRE RATING TO THE
 WALL AROUND THE VAULT AND THE EXPANSION
 VAULT.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  