| Plan Review Notes For Permit 03121694 |
| Permit Number |
03121694 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-26 00:00:00 | PROVISO: | | | PLAN SHEET M-2 A/C EQUIPMENT SCHEDULE | | | NOTE #3 "SMOKE DETECTOR MOUNTED ON | | | RETURN", PER 2001 FBC(M) 606.2.1 DUCT | | | SMOKE DETECTORS TO INSTALLED ON THE | | | SUPPLY AIR NOT THE RETURN. | | | | | | PLEASE CLARIFY THE FIRE RATING TO THE | | | WALL AROUND THE VAULT AND THE EXPANSION | | | VAULT. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|