| Plan Review Notes For Permit 03121694 |
| Permit Number |
03121694 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-02 00:00:00 | 1) SITE PLAN DOES NOT GIVE VICINITY | | | OR STREET NAME LOCATIONS. | | | | | | 2) SITE PLAN DOES NOT DISPLAY FIRE | | | HYDRANT LOCATIONS. | | | | | | 3) PLEASE EXPLAIN WHAT EFFECT THE SQUARE | | | COLUMN WILL HAVE ON EXITING FROM | | | VESTIBULE 100. | | | | | | 4) THE PROPOSED LOCATION MAY BE LOCATED | | | IN THE CITY FIRE LIMITS, CERTAIN | | | RESTRICTIONS MAY APPLY. PLEASE SEE | | | APPENDIX F, LOCAL AMENDMENTS TO THE | | | FLORIDA BUILDING CODE. | | | | | | 5) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. A MINIMUM OF 6" | | | HIGH NUMBERS ARE REQUIRED. | | | | | | 6) HANDRAILS REQUIRED ON BOTH SIDES | | | OF SERVICE STAIR. | | | | | | 7) ELECTRICAL ROOM SHALL BE ONE HOUR | | | FIRE RATED WITH 45 MINUTE OPENING | | | PROTECTED IF THE BUILDING IS NOT FIRE | | | SPRINKLER PROTECTED. | | | | | | 8) TITLE PAGE MAKES REFERENCE TO | | | BASEMENT. PLEASE ADVISE. | | | | | | 9) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|