2004-01-12 00:00:00********** UNSAT *****************
  
 1)NOTE: PLANS/ CODES REFERENCED ON PLANS
 REFER TO THE 99 NEC. PLEASE SEE THAT WE
 ARE THE 2002 NEC. PLEASE ADJUST.
  
 2)NOTE; PLEASE SEE MULTIPLE PAGES FOR
 WIND LOADING OF POLES.
 ONE SHOWS 140 MPH (REQ'D) ANOTHER,120MPH
 PLEASE SEE 2001 FBC. WE ARE UNDER 140MPH
 PLEASE ALSO SEE NOTE MENTIONS, CONTRACT-
 -OR TO PROVIDE SPECIFIC SIGNED AND SEAL-
 -ED WIND LOAD CALCS/SPECS ETC AT LATER
 DATE. PLEASE SEE THAT THIS INFORMATION
 IS REQ'D AT THIS TIME AND SHOULD BE
 SUBMITTED WHEN SUBMITTING FOR PERMIT.
  
 2)NOTE: PLANS ARE ONLY IN FOR PLAN
 REVIEW AND NOT FOR PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 3)NOTE: PLEASE