| 2004-03-18 00:00:00 | PROVISO: | | | PER THE REVISION TO THE 2001 FBC(M)601.4 | | | EFFECTIVE JUNE 30, 2003: | | | | | | WHEN CALCULATING RETURN AIR FROM THE | | | MASTER BEDROOM ALL SUPPLY AIR INTO THE | | | SUITE IS TO BE INCLUDED FOR THE TOTAL OF | | | SUPPLY AIR. | | | I.E., 10" SUPPLY TO BEDROOM = 78 SQ IN | | | 4""MASTER CLOSET = 13 SQ IN | | | 4""MASTER BATHRM = 13 SQ IN | | | TOTAL = 104 SQ IN X 1.5 = 156 SQ IN = | | | 15" RETURN AIR JUMPER. | | | | | | PLEASE REVISE RETURN AIR FOR THE MASTER | | | BEDROOM TO REFLECT THE REQUIRED SIZE FOR | | | A RETURN AIR JUMPER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|