| 2004-02-10 00:00:00 | BUILDING PLAN REVIEW FAILED: |
| | |
| | 1.PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE |
| | WEBSITEWWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 2. PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE |
| | USED FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 3. SHOW DETAIL @ SECTION AT FRONT |
| | PORCH ENTRY TO SHOW TIE-IN TO GABLE. |
| | |
| | 4. SPECIAL ROOF SHEATHING NAILING ZONE |
| | COMPLYING WITHREVISED TABLE 2306.1 |
| | FASTENING SCHEDULE WPB AMENDMENTS TO FBC |
| | |
| | 5.SPECIFY LIVE LOAD BOTTOM CORD TRUSS |
| | FOR STORAGE OR NO STORAGE PER TABLE |
| | 1604.1 : |
| | ATTIC WITH STORAGE30 PSF |
| | ATTIC WITHOUT STORAGE 10 PSF |
| | |
| | 6. PRODUCT APPROVAL FOR CLOPLAY GARAGE |
| | DOOR IS INCLUDED WITH APPLICATION.NO |
| | GARAGE SHOWN ON PLANS.REMOVE FROM |
| | PACKAGE. |
| | |
| | 7. FRONT EXTERIOR DOOR PRODUCT APPROVAL |
| | MISSING. NOTE: PAPER WORK SUBMITTED |
| | REFERS TO ENTERGYENTRY SYSTEMS. NO |
| | RECORD OF SBCCI OR MIAMI DADE PRODUCT |
| | APPROVALS SUBMITTED OR STATE PRODUCT |
| | APPROVAL. |
| | |
| | |
| | |
| | 8. A LETTER SIGNED & SEALED BY ENGINEER |
| | THAT STATES SOIL PREPARATION WAS |
| | COMPLETED AND BEARING VALUE OF 2000 PSF |
| | HAS BEEN ACHIEVED BEFORE CONSTRUCTION. |
| | |
| | 9. HOUSE WILL BE CONSTRUCTED ACCORDING |
| | TO THE 2001 FBC AND WPB AMENDMENTS. |
| | |
| | ANY QUESTIONS PLEASE CALL: |
| | LEA SMITH, BUILDING PLANS EXAMINER |
| | 805-6713 |