| 2004-04-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | A) FROM PREVIOUS REVIEW: COMMENT NUMBER |
| | SHALL REMAIN THE SAME TO AVOID CONFUSION |
| | 2) SHOW COMPLIANCE WITH SECTION 11-9.1.2 |
| | ACCESSIBLE UNITS, SLEEPING ROOMS, AND |
| | SUITES. - RESPONSE NOTED, BUT THE SHOWER |
| | SHOWN IN THESE THREE UNITS ARE NOT ROLL- |
| | IN SHOWERS. SEE ATTACHED SHEET, FIG. 57, |
| | SHOWING EXAMPLE OF ROLL-IN SHOWER. |
| | 4) SHOW COMPLIANCE WITH SECTION 11-9.1.4 |
| | CLASSED OF SLEEPING ACCOMMODATIONS. RE- |
| | SPONSE NOTED, PLEASE INDICATE TYPES OF |
| | SLEEPING ACCOMMODATION AVAILABLE TO CON- |
| | FIRM THAT ALL CLASSES ARE REPRESENTED. |
| | 7) SHT P-1 CLEANOUTS REQUIRED NEAR JUNC- |
| | TION OF BLDG DRAIN AND BLDG SEWER. 2-WAY |
| | C/O'S MAY BE USED. 708.3.5 - RESPONSE |
| | NOTED, BUT CLEANOUTS ARE NOT SHOWN. ALSO |
| | SHOW CLEANOUTS MENTIONED ABOVE ON BLDG |
| | DRAIN ISOMETRIC SHEET P-8. |
| | 8) SHT P-1 ALL UNITS, ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. KITCHEN SINK SHALL DISCHARGE |
| | DOWN-STREAM OF THE WET VENT. 909.1 - |
| | RESPONSE NOTED - PLEASE HAVE CHANGES |
| | REFLECTED ON THE SANITARY RISER DIAGRAM |
| | ALSO. |
| | 18- F. DELIVERY PRESSURE NOT INDICATED |
| | ON PLANS. INDICATE THE DELIVERY PRESSURE |
| | (PSI) PER FBC-2001 FUEL GAS CODE SECTION |
| | 402.2. |
| | |