| 2004-04-23 00:00:00 | 1) TACTILE SIGNAGE REQUIRED AT EXIT |
| | DOOR LOCATIONS. |
| | |
| | 2) ALL SHAFTWAYS LARGE ENOUGH FOR |
| | PERSONS TO FALL INTO MUST BE IDENTIFIED |
| | BY SIGNAGE "SHAFTWAY". |
| | |
| | 3) KNOX-BOX LOCKING CAPS REQUIRED |
| | ON FIRE DEPARTMENT CONNECTION. |
| | |
| | 4) PANIC HARDWARE REQUIRED ON EXIT |
| | DOORS LOCATED FOR THE POOL DECK. |
| | |
| | 5) WHAT PREVENTS PERSONS FROM LEAVING |
| | THE EXTERIOR DOOR NEAR SUITE 105 AND |
| | GOING DIRECTLY INTO THE VEHICULAR EXIT |
| | DRIVE LANE. |
| | |
| | 6) ARE THE STAIRS ON THE ROOF TERRACE |
| | SLIP RESISTANT? |
| | |
| | 7) THE BUILDING ADDRESS IS NOTED ON |
| | THE FRONT ELEVATION. WILL THE LOCATION |
| | BE CLEARLY VISIBLE AT ITS MOUNTING |
| | HEIGHT. PLEASE ADVISE. |
| | |
| | 8) SIGNS REQUIRED IN STAIRWELLS |
| | INDICATING STAIR IDENTITY, TERMINUS |
| | LOCATIONS AT TOP AND BOTTOM, ETC. |
| | |
| | 9) ALL FIRE RATED DOORS SHALL BE |
| | EQUIPED WITH SELF-CLOSING DEVICES |
| | TO CAUSE THE DOORS TO POSITIVELY LATCH. |
| | |
| | 10) SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR FIRE ALARM SYSTEM AND |
| | FIRE SPRINKLER SYSTEM. |
| | |
| | 11) WHAT PREVENTS VEHICULAR DAMAGE |
| | TO THE FIRE-LINE BACKFLOW DEVICE. |
| | |
| | 12) THE MINIMUM SIZE FIRE LINE SHALL |
| | BE AT LEAST 6 INCHES. ON SHEET FP1 |
| | THREE INCH LINES ARE SHOWN. PLEASE |
| | ADVISE. |
| | |
| | 13) THE REQUIRED FIRE ALARM SYSTEM SHALL |
| | UL LISTED FOR CENTRAL STATION SERVICE. |
| | |
| | 14) THE FIRE ALARM SYSTEM CIRCUITS |
| | SHALL BE CLASS A, STYLE D OR FULLY |
| | ADDRESSABLE. |
| | |
| | 15) NO ELECTRICAL ALLOWED IN STAIRWELL |
| | EXCEPT REQUIRED EMERGENCY LIGHTING |
| | EQUIPMENT FOR THE STAIRWELLS. |
| | |
| | 16) THE FIRE PUMP ROOM IS REQUIRED |
| | TO HAVE EMERGENCY LIGHTING. |
| | |
| | 17) REQUIRED SMOKE DETECTORS APPEAR |
| | TO BE MISSING FROM SEVERAL UNITS |
| | LOCATED ON THE SECOND FLOOR. SOME |
| | UNITS HAVE SMOKE DETECTORS IN THE |
| | HALLWAY AND SOME DO NOT. PLEASE |
| | EXPLAIN RATIONALE. |
| | |