| 2004-05-11 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 2/17/04: |
| | |
| | 1) HANDWRITTEN RESPONSE ON COMMENT SHEET |
| | IS NOTED.THE NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | |
| | 2) HANDWRITTEN COMMENT RESPONSE IS NOTED |
| | IMPACT FEES. THE PLANS SHALL BE TAKEN TO |
| | PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC* 105.13.1SPECIAL INSPECTOR. |
| | SUBMITTAL OF THE STRUCTURAL INSPECTION |
| | PLAN IS NOTED.SIGNED/SEALED COPIES OF |
| | THE THRESHOLD INSPECTOR AGREEMENT MUST |
| | ALSO BE SUBMITTED BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED.BLANK FORMS ARE |
| | AVAILABLE FROM THIS OFFICE IF REQUIRED. |
| | THREE COPIES OF ALL PLANS AND OTHER |
| | DOCUMENTS ARE REQUIRED FOR PERMITTING |
| | PURPOSES. |
| | |
| | 5) FBC TABLE 600FIRE RESISTANCE RATING |
| | FOR TYPE II CONSTRUCTION.SHEET A-101, |
| | THE COMMENT RESPONSE, REVISING THE |
| | CONSTRUCTION TYPE IS NOTED, BUT IT IS |
| | SHOWN AS "TYPE II (1 HOUR PROTECTED)". |
| | THE REQUIRED FIRE RESISTANCE RATINGS FOR |
| | THE STRUCTURAL ELEMENTS OF A TYPE II |
| | BUILDING EXCEED 1 HOUR.REMOVE THE |
| | REFERENCE TO "(1 HOUR PROTECTED)" FROM |
| | SHEETS A-101, A-117, A-118, A-119 AND |
| | A-120. |
| | NOTE: ALSO, FOR TYPE II CONSTRUCTION, |
| | THE EAST AND WEST WALLS ARE REQUIRED TO |
| | HAVE A 3-HOUR FIRE RESISTANCE RATING AS |
| | THEY ARE WITHIN 3 FEET OF THEIR |
| | RESPECTIVE PROPERTY LINE.AMEND SHEETS |
| | A-117, A-118 AND A-119. |
| | |
| | 11) FBC 11-9.1.2ACCESSIBLE UNITS. |
| | THE COMMENT RESPONSE ADDED TO |
| | SHEET A-101 IS NOTED, BUT IS NOT FULLY |
| | CODE COMPLIANT AS FOLLOWS: |
| | (A) FBC 11-9.2.2(3) & (6)DOOR WIDTHS. |
| | BATHROOM DOORS 204, 207 AND 266 SHALL |
| | HAVE AT LEAST 32 INCHES CLEAR OPENING |
| | WITH THE DOOR OPEN 90 DEGREES MEASURED |
| | BETWEEN THE FACE OF THE DOOR AND THE |
| | OPPOSITE STOP.DOOR SCHEDULE A-604 |
| | SHOWS 2'-8" WIDE DOORS.AMEND THE |
| | SCHEDULE. |
| | (B) FBC 11-9.2.2(4) ACCESSIBLE STORAGE. |
| | FOR THE ACCESSIBLE ROOMS/SUITES, AMEND |
| | THE PLANS TO DEMONSTRATE COMPLIANCE WITH |
| | THE REQUIREMENT FOR ACCESSIBLE CLOSETS/ |
| | SHELVES.SEE ALSO FBC 11-4.25 |
| | (C) FBC 11-9.2.2(7)KITCHEN COUNTER/ |
| | SINK/CABINETS.FOR THE ACCESSIBLE |
| | ROOMS/SUITES, AMEND THE PLANS TO |
| | DEMONSTRATE COMPLIANCE WITH THE |
| | REQUIREMENT FOR A MAXIMUM HEIGHT OF 34", |
| | ABOVE FINISH FLOOR, FOR THE THE COUNTER/ |
| | SINK AND FOR 50% OF THE STORAGE SPACE IN |
| | CABINETS AND FRIDGE-FREEZER TO BE WITHIN |
| | THE REACH RANGES OF FBC 11-4.2.5 AND |
| | FBC 11-4.2.6 |
| | |
| | 20) FBC* TABLE 2306.1SHEET A-501, |
| | DETAIL 2. THE COMMENT RESPONSE IS NOTED. |
| | THE DETAIL STILL SHOWS 5/8" PLYWOOD, |
| | OVER CORRUGATED GALVANIZED METAL DECK, |
| | NAILED TO "SUPPORT" WITH 8D COMMON |
| | NAILS.THE PROPOSED 8D COMMON NAILS ARE |
| | NOT APPROPRIATE FOR FIXING THE 5/8" |
| | PLYWOOD TO CORRUGATED GALVANIZED METAL |
| | DECK.AMEND THE DETAIL. |
| | |
| | 22) SHEET S-9 CONNECTORS SCHEDULE AND |
| | SHEET S-11 SECTION 2.THE COMMENT |
| | RESPONSE REVISING THE SCHEDULE IS NOTED, |
| | BUT THE SCHEDULE NOW SHOWS THAT THE |
| | UPLIFT CAPACITY OF TWO META22 (AND TWO |
| | HETAL20) EMBEDDED ANCHOR IS ASSUMED TO |
| | BE TWICE THAT OF A SINGLE ANCHOR. |
| | REFERENCE TO THE 2004 SIMPSON CATALOGUE |
| | WILL SHOW THAT A DOUBLE EMBEDDED ANCHOR |
| | INSTALLATION DOES NOT HAVE DOUBLE THE |
| | UPLIFT CAPACITY OF A SINGLE ANCHOR |
| | INSTALLATION IF THE FAILURE MODE IS |
| | CONCRETE CONE PULL-OUT.AMEND THE |
| | SCHEDULE. |
| | |
| | 23) PROVISO: |
| | SHEETS A-502 & A-505, PLANTER AND |
| | OBELISK ATTACHMENT DETAILS.ADDITION OF |
| | DETAILS 15 AND 16 (SHEET S-10) IS NOTED. |
| | THE SHOP DRAWINGS SHALL BE SUBMITTED TO |
| | THE THIS OFFICE FOR REVIEW. |
| | |
| | 25) FBC 13-103.1.2THIS COMMENT HAS NOT |
| | BEEN PROPERLY ADDRESSED.BEFORE A |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | ALSO, ADD THE OWNER'S NAME AND THE ZIP |
| | CODE (33401) TO THE PROJECT INFORMATION |
| | ON SHEET 1. |
| | |
| | 26) FBC 13-103.1.1.1THIS COMMENT HAS |
| | NOT BEEN PROPERLY ADDRESSED. THE |
| | PROFESSIONAL RESPONSIBLE FOR THE DESIGN |
| | OF THE ELECTRICAL SYSTEMS SHALL ALSO |
| | SIGN THE ENERGY CODE COMPLIANCE FORM, |
| | AND ADD HIS LICENSE, NUMBER TO CERTIFY |
| | COMPLIANCE. |
| | |
| | 27) PRODUCT APPROVALS.SUBMITTAL OF ONE |
| | COPY OF THE STATEWIDE PRODUCT APPROVAL |
| | LISTING COVER SHEET IS NOTED FOR THE |
| | FIXED WINDOWS, CASEMENT WINDOWS, |
| | EXTERIOR DOORS, STORM PANEL SHUTTERS, |
| | ROOF TILE, ROOF UNDERLAYMENT AND ROOF |
| | MEMBRANE.SUBMIT THREE COPIES OF ALL |
| | PRODUCT APPROVALS WITH THE PROPOSED |
| | PRODUCTS, SIZES AND OPTIONS HIGHLIGHTED. |
| | ALSO, SUBMIT PRODUCT APPROVALS FOR THE |
| | PROPOSED 4-PLY BUILT-UP ROOF SYSTEM, THE |
| | EXTERIOR METAL SINGLE DOORS AND THE |
| | MULLIONS (OR STOREFRONT) FOR THE |
| | RESTAURANT AND COURTYARD TRANSOMS. |
| | THE FOLLOWING COMMENTS APPLY TO THOSE |
| | STATEWIDE PRODUCT APPROVAL LISTINGS THAT |
| | WERE ALREADY SUBMITTED: |
| | (A) FRENCH DOORS.THE SUBMITTAL OF |
| | STATEWIDE PRODUCT APPROVAL LISTING COVER |
| | SHEET FL253 IS NOTED.THE LISTING IS |
| | FOR THREE DIFFERENT DOOR TYPES AND |
| | REFERS TO A SEPARATE MIAMI-DADE PRODUCT |
| | APPROVAL FOR EACH ONE.MARK THE LISTING |
| | TO SHOW WHICH DOOR TYPE IS PROPOSED AND |
| | INCLUDE THREE COPIES OF THE RELEVANT |
| | MIAMI-DADE PRODUCT APPROVAL. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE, |
| | WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH |
| | _APP.ASP |
| | (B) FIXED WINDOWS.THE SUBMITTAL OF |
| | STATEWIDE PRODUCT APPROVAL LISTING COVER |
| | SHEET FL243 IS NOTED.THE LISTING IS |
| | FOR EIGHT DIFFERENT WINDOW TYPES AND |
| | REFERS TO A SEPARATE MIAMI-DADE PRODUCT |
| | APPROVAL FOR EACH ONE.MARK THE LISTING |
| | TO SHOW WHICH WINDOW TYPE IS PROPOSED |
| | AND INCLUDE THREE COPIES OF THE RELEVANT |
| | MIAMI-DADE PRODUCT APPROVAL. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE, |
| | WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH |
| | _APP.ASP |
| | (C) CASEMENT WINDOWS.THE SUBMITTAL OF |
| | STATEWIDE PRODUCT APPROVAL LISTING COVER |
| | SHEET FL245 IS NOTED.THE LISTING IS |
| | FOR FOUR DIFFERENT WINDOW TYPES AND |
| | REFERS TO A SEPARATE MIAMI-DADE PRODUCT |
| | APPROVAL FOR EACH ONE.MARK THE LISTING |
| | TO SHOW WHICH WINDOW TYPE IS PROPOSED |
| | AND INCLUDE THREE COPIES OF THE RELEVANT |
| | MIAMI-DADE PRODUCT APPROVAL. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE, |
| | WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH |
| | _APP.ASP |
| | (D) CLAY ROOF TILE.THE SUBMITTAL OF |
| | STATEWIDE PRODUCT APPROVAL LISTING COVER |
| | SHEET FL738 IS NOTED.THE LISTING |
| | PROVIDES A WEB-LINK TO THE SBCCI |
| | EVALUATION REPORT DOCUMENT USED TO |
| | EVALUATE THE PRODUCT.INCLUDE THREE |
| | COPIES OF THE SBCCI EVALUATION REPORT |
| | MARKED TO SHOW WHICH PRODUCT IS TO BE |
| | USED. |
| | (E) STORM SHUTTER.THE SUBMITTAL OF |
| | STATEWIDE PRODUCT APPROVAL LISTING COVER |
| | SHEET FL347 IS NOTED.THE LISTING |
| | PROVIDES A WEB-LINK TO THE MIAMI-DADE |
| | PRODUCT APPROVAL DOCUMENT USED TO |
| | EVALUATE THE PRODUCT.INCLUDE THREE |
| | COPIES OF THE MIAMI-DADE PRODUCT |
| | APPROVAL MARKED TO SHOW WHAT SPAN AND |
| | ANCHOR SPACING IS PROPOSED. ON WHICH |
| | OPENINGS ARE THEY TO BE USED?NOTE: FOR |
| | COMMERCIAL STRUCTURES, REMOVABLE STORM |
| | PANELS MAY NOT BE USED ABOVE THE FIRST |
| | (GROUND) FLOOR. |
| | |
| | 29) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |