| 2004-02-20 00:00:00 | DENIED: |
| | 1.PLAN SHEET AC-2, FIRE DAMPERS ON |
| | THE SUPPLY DUCT TO AHU-1 & EF-5 ARE |
| | INDICATED IN THE MIDDLE OF THE CORRIDOR |
| | AND NOT IN THE RATED WALL.PLEASE |
| | RELOCATE. |
| | |
| | 2.PLAN SHEET AC-2, EXHAUST FROM THE |
| | DRYER RUNS TO A PLENUM BOX.PLEASE |
| | CLARIFY TERMINATION OF EXHAUST. |
| | |
| | 3.DUCTS PENETRATING ONE FLOOR SHALL |
| | BE PROTECTED BY A FIRE DAMPER AT FLOOR |
| | PENETRATION.DUCTS PENETRATING MORE |
| | THAN ONE FLOOR SHALL BE PROTECTED BY A |
| | SHAFT ENCLOSURE PER 2001 FBC(M) 607.4. |
| | |
| | 4.AC-3 DUCTS PENETRATING RATED WALLS |
| | WITHOUT FIRE DAMPERS SHALL COMPLY WITH |
| | 2001 FBC(M) 607.1.3 #3 ITEMS 1 THROUGH |
| | 4. SOME DUCTS ARE LESS THAN 5 FT BEFORE |
| | AN OPENING.PLEASE CLARIFY. |
| | |
| | 5.PLAN SHEET AC-6, EXHAUST RISERS |
| | APPEAR TO TERMINATE BELOW THE ROOF, |
| | PLEASE CLARIFY.PROVIDE DETAIL OF |
| | CAP/FAN FOR ROOF TERMINATION. |
| | |
| | 6.PLEASE INDICATE WHAT WILL BE STORED |
| | IN THE POOL/SPA EQUIPMENT ROOM. |
| | PROVIDE INFORMATION AND AMOUNTS OF ANY |
| | CHEMICALS THAT MAY BE STORED IN THIS |
| | AREA. |
| | |
| | 7.PLEASE PROVIDE COMBUSTION AIR |
| | CALCULATIONS FOR THE GAS WATER HEATERS. |
| | PROVIDE DETAIL FOR THE VENTING OF |
| | WATER HEATERS. |
| | |
| | 8.PLAN SHEET A-102 INDICATES FUTURE |
| | KITCHEN/RESTAURANT, NO INDICATION OF |
| | WHERE THE EXHAUST FOR THE HOOD MIGHT |
| | TERMINATE.PLEASE NOTE, TERMINATION |
| | FOR GREASE DUCT SHALL COMPLY WITH 2001 |
| | FBC(M) 506.3.14.3.EXHAUST SHALL NOT |
| | TERMINATE WHERE PROTECTED OPENINGS ARE |
| | REQUIRED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |