| 2004-01-22 00:00:00 | 1) TAMPER SWITCHES, CHAIN AND LOCK |
| | ARE REQUIRED ON FIRE LINE BACKFLOW |
| | DEVICE. |
| | |
| | 2) PROPOSED FIRE DEPARTMENT CONNECTION |
| | SHALL BE BE WITHIN 150 FEET OF A |
| | FIRE HYDRANT. |
| | |
| | 3) A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 4) A TEMPORARY STANDPIPE WILL BE |
| | REQUIRED WHEN THE BUILDING REACHES |
| | THREE STORIES OR THIRTY FEET IN |
| | HEIGHT. |
| | |
| | 5) STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 6) WILL THE PARALLEL PARKING SPACES |
| | ON FERN STREET INTERFERE WITH THE |
| | FIRE DEPARTMENT CONNECTION LOCATION. |
| | |
| | 7) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 8) PLEASE INDICATE ALL FIRE |
| | EXTINGUISHER LOCATIONS. |
| | |
| | 9) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWING. A MINIMUM 6" HIGH |
| | NUMBERS ARE REQUIRED. |
| | |
| | 10) PLEASE INDICATE PRESCRIPTIVE |
| | CODE REQUIREMENTS FOR ALL HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 11) EMERGENCY INSTRUCTIONS ARE REQUIRED |
| | IN EACH GUESTROOM. |
| | |
| | 12) NO COMBUSTIBLES ARE ALLOWED IN |
| | RETURN AIR PLENUMS. |
| | |
| | 13) SOME EXIT SIGNS APPEAR TO BE |
| | MISSING FROM PAGE E-1. |
| | |
| | 14) EMERGENCY LIGHTS NEEDED IN BATHROOMS |
| | ON FIRST FLOOR. |
| | |
| | 15) EMERGENCY LIGTING REQUIRED IN FIRE |
| | PUMP ROOM. |
| | |
| | 16) SMOKE DETECTORS APPEAR TO BE |
| | MISSING IN SEVERAL LOCALES ON PAGE E-3. |
| | |
| | 17) FUTURE RESTAURANT AREA IS TO BE |
| | FIRE SPRINKLER PROTECTED PRIOR TO |
| | HOTEL REQUESTING A C OF O. |
| | |
| | 18) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER AND FIRE ALARM |
| | SYSTEM. |
| | |
| | 19) SHAFTS LARGE ENOUGH FOR PERSONS |
| | TO FALL INTO SHALL BE MARKED SHAFTWAY. |
| | |
| | 20) PLEASE INDICATE ROOMS DESIGNATED |
| | FOR THE HEARING IMPAIRED AND DESIGNATE |
| | FIRE ALARM VISUAL DEVICES. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |