| 2004-02-11 00:00:00 | *************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE 210.60A AND 210.52 |
| | FOR RECEPT SPACING IN UNITS/ROOMS. |
| | THERE ARE MANY MISSING FOR 2' OF WALL |
| | SPACE AND W/IN 6' OF DOORWAYS. |
| | |
| | 2)NOTE: PLEASE PROVIDE NOTE ON PLANS |
| | FOR REQUIRED BUSWAY/BUSDUCT CURBING PER |
| | 368.8B(2) |
| | |
| | 3)NOTE: PLEASE CLARIFY USEAGE. PERMIT |
| | APPLICATION AND PLANS CALL FOR A NEW |
| | 5 STORY HOTEL. ELECTRICAL PLANS HAVE |
| | EACH INDIVIDUAL UNIT ON A SEPARATE |
| | ELECTRICAL METER FROM FPL. PLEASE |
| | PROVIDE INFORMATION FROM FPL AND OR HOW |
| | THIS FITS INTO BEING A HOTEL? IS BILLING |
| | FOR ALL METERS GOING TO ONE OWNER? ARE |
| | THESE "EXTENDED STAY" UNITS? ETC |
| | PLEASE PROVIDE FPL'S CONFORMATION OF |
| | THIS. |
| | THIS IS ALSO PROVIDING A POINT IN THE |
| | UDP TO RUN POWER TO OTHER LOCALS W/OUT |
| | BEING METERED FROM FPL.PLEASE VERIFY |
| | ALL OF THE ABOVE. |
| | |
| | 4)NOTE: PLEASE PROVIDE ALL INFORMATION |
| | ON PLANS AND TITLE BLOCKS PER FAC |
| | 61G1-16.004 FOR ARCH'S. THE ADDRESS |
| | IS REQ'D ON PLANS/ TITLE BLOCK. |
| | PLEASE ALSO SEE LICENSE INFORMATION FOR |
| | ARCH'S FIRM IS MISSING AS REQ'D PER |
| | ABOVE. PLEASE ALSO SEE FS 481.219 FOR |
| | REQ'D CERTIFICATE OF AUTHORIZATIONFOR |
| | |
| | 5)NOTE: PLANS SHOW NEW POOL, HOWEVER |
| | POOL IS REQ'D TO BE UNDER A SEAPARATE |
| | PERMIT. |
| | PLEASE PROVIDE NOTE ON PLANS IN FOR |
| | TIMES OF PERMITTED SWIMMING. IF SWIMMING |
| | IS GOING TO BE AFTER DUSK. A PHOTOMETRIC |
| | STUDY WILL BE REQUIRED AND PLANS WILL |
| | ALSO REQ'D TO BE STAMPED BY THE PALM |
| | BEACH COUNTY HEALTH DEPT. |
| | |
| | 6)NOTE:PLEASE SEE PANEL "HA", SHOW CIR- |
| | -CUIT FOR DRYER AT 5KW, HOWEVEROCP |
| | IS SHWON AT 2P-20A? |
| | |
| | 7)NOTE: PLEASE SEE "DWELLING UNIT" |
| | DEFINITION IN NEC AND OTHER CODES. |
| | PLEASE SEE USAGE AND THE AMOUNT OF |
| | LAUNDRY FIXTURES REQ'D. |
| | PLEASE SEE PLUMB COMMENTS. |
| | THIS QUESTION WILL COINCIDE WITH NOTE |
| | #3 ABOVE. |
| | |
| | 8)NOTE: PLEASE "UDP", SHOWN AS BEING MLO |
| | WITH TWO MAINS IN EQUIPMENT, HOWEVER |
| | "UDP" IS SHOWN AS HAVING 42 SPACES?? |
| | PLEASE SEE THIS IS NOT PERMITTED DUE TO |
| | THE AMOUNT OF SPACES FOR A POSSIBLE |
| | ADDITION OF 33 MORE MAINS? (1P BRKRS). |
| | PLEASE SEE 230.71.A MCB MAY BE INSTALL |
| | -ED? |
| | |
| | 9)NOTE: PLEASE SEE ALL PANEL SCHEDULES, |
| | FEEDERS/ RISER DIAGRAM IS MISSING |
| | EQUIPMENT GROUNDING CONDUCTORS PER |
| | 250.110,250.24 ETC , SIZE PER 250.122 |
| | |
| | 10)NOTE: PLEASE PROVIDE COMPLETE FIXTURE |
| | SCHEDULE. |
| | |
| | 11)NOTE: PLEASE SEE AREAS REQUIRED TO |
| | MEET 700.16. |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS |
| | FOR EM/EXT LTS REQUIRED. SEE EM/EXT FIX- |
| | -TURES SHOWN INDICATE HAVING AN EMERGEN- |
| | -CY BALLAST,HOWEVER NO INDICATION OF |
| | BATTERY BACK UP PER 700.12 |
| | |
| | 12)NOTE: PLEASE INDICATE/SHOW ALL HEIGHT |
| | -S FOR ALL ELECTRICAL DEVICES PER |
| | FHAR 24CFR 100.205. (FAIR HOUSING) |
| | |
| | 13)NOTE: PLEASE PROVIDE ALL INFORMATION |
| | FOR FIRE PUMP. PLEASE ALSO PROVIDE |
| | INFORMATION ON RISER DIAGRAM FOR FIRE |
| | PUMP. PLEASE SEE 695.4B1 |
| | PLEASE ALSO SEE 230.76, 230.79 FOR |
| | DISCONNECTING MEANS. PLEASE ALSO NOTE |
| | SIGNAGE FOR FIRE PUMP/LOCATION ETC IS |
| | REQ'D TO BE NOTED ONPLANS.(SIGNAGE) |
| | |
| | 14)NOTE: PLEASE SEE RISER DIAGRAMS SHOWS |
| | FUTURE CONDUITS FOR RESTARUANT, YET |
| | ON THE RIGHT HAND SIDE OF E-7 , NOTE |
| | MENTIONS A 3P-400A MCB? PLEASE CLARIFY |
| | IF A MAIN IS GOING TO BE INSTALLED AT |
| | THIS TIME. IF SO, PLEASE PROVIDE INFOR- |
| | -MATION FOR DISC. IF NOT, PLEASE ADJUST. |
| | |
| | 15)NOTE: PLEASE SEE GUTTER SIZE SHOWN, |
| | RISER APPEAR TO BE A MISPRINT FOR THE |
| | SIZE OF 12"X12"X6",, SHOULD BE 6'? |
| | |
| | 16)NOTE: PLEASE SEE PANEL "HB", SHOWN |
| | AS 22.5 A'S. (MISPRINT)? 225A'S. |
| | "HB" HAS 200A OCP FEED. |
| | |
| | 17)NOTE: PLEASE NOTE ON PLANS ALL |
| | ELECTRICAL WORK TO MEET 2002 NEC. |
| | |
| | 18)NOTE: PLEASE SEE LOAD CALCULATIONS |
| | ON E-6, SHOWN AS 48 UNITS? PLEASE VERIFY |
| | THE OTHER 8 MISSING UNITS? |
| | 215.5 |
| | |
| | 19)NOTE: PLEASE SEE 215.3,230.42 ETC, |
| | ALL CONTINUOUS LOADS ARE ALSO TO BE |
| | SHOWN AT 125%, NOT JUST THE LARGEST |
| | MOTOR LOAD. |
| | |
| | 20)NOTE: PLEASE SEE THAT ELEVATOR MAINS |
| | ARE SHOWN AS ELEV 1,2 WHICH IS FINE. |
| | HOWEVER, THEY ARE ALSO MAINS 5,6? |
| | PLEASE ADJUST NOTES. |
| | |
| | 21)NOTE: PLEASE SEE SD LOCATIONS TO |
| | MEETNFPA-72 8-1.4.1.6.2 |
| | PLEASE SEE 8-1.4.2, SD'S REQUIRMENTS |
| | W/IN 20'OF COOKING APPLIANCES. PLEASE |
| | ALSO SEE 3' FROM BATH DOORS. PLEASE |
| | SEE WHICH TYPE ARE PERMITTED. |
| | |
| | PLEASE SEE ONE SET OF PLANS HAVE MOST |
| | ITEMS HIGHLIGHTED. PLEASE SEE, RAILING |
| | AREA OF SECOND FLOOR MEZZ UNITS ARE |
| | CONSIDERED WALL SPACE PER NEC, AND ARE |
| | REQ'D TO MEET 210.52 ALSO. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |