| 2006-06-19 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THIS REVISION MARKED AS SHEET "E-1", |
| | THE SHEET IT IS INTENDED TO REVISE IS |
| | "A-3" IN THE ORIGINAL SET OF PERMITTED |
| | DOCUMENTS. PLEASE CORRECT. |
| | |
| | 2} THE EQUIPMENT GROUNDING CONDUCTOR |
| | MUST COMPLY WITH 250.66. |
| | |
| | 3} THIS PLANS PANEL SCHEDULE INDICATES " |
| | NEW PANEL"A", AND "EXISTING PANEL "B". |
| | THE ORIGINAL REVIEW FOR THIS PROJECT, |
| | DONE ON 1/15/2004, WAS FOR A NEW |
| | SERVICE, WITH A DISCONNECT, AND HAD THE |
| | CORRECT GEC. CORRELATE THE PLAN. ALL THE |
| | SERVICE IS NEW FOR THE PURPOSE OF THIS |
| | REVIEW, AS PERMITTED. IF THERE ARE |
| | EXISTING PANELS, THAT WERE NOT ON THE |
| | PERMITTED DOCUMENTS, THEN REVISE THE |
| | PERMITTED SET AS REVIEWED. SEE 106.4, |
| | FBC. |
| | |
| | 4} SEE 220.3(A)(4) RECESSED LUMINAIRES |
| | (LIGHTING FIXTURES). AN OUTLET SUPPLYING |
| | RECESSED LUMINAIRE(S) [LIGHTING |
| | FIXTURE(S)] SHALL BE COMPUTED BASED ON |
| | THE MAXIMUM VOLT-AMPERE RATING OF THE |
| | EQUIPMENT AND LAMPS FOR WHICH THE |
| | LUMINAIRE(S) [FIXTURE(S)] IS RATED. ADD |
| | TO THE CALCULATIONS WHEN RESUBMITTING. |
| | |
| | 5}THE SMALL APPLIANCE CALCULATION MUST |
| | BE 1500 VA PER CIRCUIT. SEE 220.16(A). |
| | |
| | 6} REVISIONS TO THE PERMITTED SET OF |
| | PLANS MUST BE DONE BY THE DESIGNER OF |
| | RECORD PER FLORIDA STATUTE 481 AND FBC. |
| | 106.1. THE ARCHITECTURAL FIRM WHO |
| | STAMPED THE ORIGINAL SET. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |