Plan Review Notes
Plan Review Notes For Permit 03121597
Permit Number 03121597
Review Stop E
Sequence Number 3
Notes
Date Text
2006-06-19 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THIS REVISION MARKED AS SHEET "E-1",
 THE SHEET IT IS INTENDED TO REVISE IS
 "A-3" IN THE ORIGINAL SET OF PERMITTED
 DOCUMENTS. PLEASE CORRECT.
  
 2} THE EQUIPMENT GROUNDING CONDUCTOR
 MUST COMPLY WITH 250.66.
  
 3} THIS PLANS PANEL SCHEDULE INDICATES "
 NEW PANEL"A", AND "EXISTING PANEL "B".
 THE ORIGINAL REVIEW FOR THIS PROJECT,
 DONE ON 1/15/2004, WAS FOR A NEW
 SERVICE, WITH A DISCONNECT, AND HAD THE
 CORRECT GEC. CORRELATE THE PLAN. ALL THE
 SERVICE IS NEW FOR THE PURPOSE OF THIS
 REVIEW, AS PERMITTED. IF THERE ARE
 EXISTING PANELS, THAT WERE NOT ON THE
 PERMITTED DOCUMENTS, THEN REVISE THE
 PERMITTED SET AS REVIEWED. SEE 106.4,
 FBC.
  
 4} SEE 220.3(A)(4) RECESSED LUMINAIRES
 (LIGHTING FIXTURES). AN OUTLET SUPPLYING
 RECESSED LUMINAIRE(S) [LIGHTING
 FIXTURE(S)] SHALL BE COMPUTED BASED ON
 THE MAXIMUM VOLT-AMPERE RATING OF THE
 EQUIPMENT AND LAMPS FOR WHICH THE
 LUMINAIRE(S) [FIXTURE(S)] IS RATED. ADD
 TO THE CALCULATIONS WHEN RESUBMITTING.
  
 5}THE SMALL APPLIANCE CALCULATION MUST
 BE 1500 VA PER CIRCUIT. SEE 220.16(A).
  
 6} REVISIONS TO THE PERMITTED SET OF
 PLANS MUST BE DONE BY THE DESIGNER OF
 RECORD PER FLORIDA STATUTE 481 AND FBC.
 106.1. THE ARCHITECTURAL FIRM WHO
 STAMPED THE ORIGINAL SET.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  