Plan Review Notes
Plan Review Notes For Permit 03121597
Permit Number 03121597
Review Stop M
Sequence Number 1
Notes
Date Text
2004-01-21 00:00:00DENIED:
 1.PLEASE PROVIDE ENERGY AND MAUNAL J
 CALCULATIONS PER 2001 FBC CHAPTER 13
 SUB CHAPTER 600.
  
 2. INDICATE DUCT/GRILLE SIZE AND LAYOUT.
  
 3. INDICATE NEW OR EXISTING EQUIPMENT.
 PROVIDE MAKE, MODEL, BTU OF THE AHU AND
 SEER OF THE CONDENSING UNIT.
  
 4.PLEASE NOTE, RETURN AIR REQUIRED
 FROM THE MASTER BEDROOM PER 2001 FBC(M)
 601.4.ALL SUPPLY AIR TO THE MASTER
 SUITE TO BE INCLUDED FOR THE PROPER
 SIZING OF RETURN AIR.SEE THE ATTACHED
 SCHEDULE FOR SIZING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.