| Plan Review Notes For Permit 03121597 |
| Permit Number |
03121597 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-21 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE ENERGY AND MAUNAL J | | | CALCULATIONS PER 2001 FBC CHAPTER 13 | | | SUB CHAPTER 600. | | | | | | 2. INDICATE DUCT/GRILLE SIZE AND LAYOUT. | | | | | | 3. INDICATE NEW OR EXISTING EQUIPMENT. | | | PROVIDE MAKE, MODEL, BTU OF THE AHU AND | | | SEER OF THE CONDENSING UNIT. | | | | | | 4.PLEASE NOTE, RETURN AIR REQUIRED | | | FROM THE MASTER BEDROOM PER 2001 FBC(M) | | | 601.4.ALL SUPPLY AIR TO THE MASTER | | | SUITE TO BE INCLUDED FOR THE PROPER | | | SIZING OF RETURN AIR.SEE THE ATTACHED | | | SCHEDULE FOR SIZING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|