2004-10-06 00:00:00********* UNSAT 2ND REVIEW ***********
  
 PLEASE SEE MOST OF THE SAME NOTES FROM
 FIRST REVIEW STILL NEED TO BE CORRECTED.
 SAME PLANS CAME BACK WITH NO CHANGES
 MADE??
  
 1)NOTE: PLEASE SEE NOTE #1 IS OK
  
 2)NOTE: PLEASE SEE LOAD CALCS WERE
 SUBMITTED ON SEPARATE SHEET, HOWEVER
 PLEASE SEE 220.31B FOR REQUIRED LOAD
 CALCULATION FOR EXSITING DWELLING.
 PLEASE CORRELATE LOAD CALCS WITH PANEL
 SCHEDULE AND PLANS.
 PLEASE SEE 220.18 FOR DRYER LOAD.
 PANEL SCHEDULE TO INCLUDE AWG,OCP FOR
 ALL MIN CIRCUITS REQUIRED.
 SEE NOTE #3 PREVIOUS REVIEW.
  
 3)NOTE: PLEASE SEE NOTES:4,5 PREVIOUS
 REVIEW.
  
 4)NOTE: PLEASE SEE FBC CHAPTER 34
 3401.7.1.2.1 PLEASE INDICATE NEW OR
 EXISTING SD'S AND GFI RECEPTS IN EXIST-
 -ING DWELLING TO MEET CODE.
 SD'D REQUIRED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS. NFPA-72 8-1.4.1.6.2
  
 5)NOTE: PLEASE SEE FS 553.80(2)(B)
 ATTACHED WITH RESPECT TO DESIGN PROFESS-
 -IONAL. THIS IS ONLY A NOTICE GIVEN AT
 THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]