| 2004-10-06 00:00:00 | ********* UNSAT 2ND REVIEW *********** |
| | |
| | PLEASE SEE MOST OF THE SAME NOTES FROM |
| | FIRST REVIEW STILL NEED TO BE CORRECTED. |
| | SAME PLANS CAME BACK WITH NO CHANGES |
| | MADE?? |
| | |
| | 1)NOTE: PLEASE SEE NOTE #1 IS OK |
| | |
| | 2)NOTE: PLEASE SEE LOAD CALCS WERE |
| | SUBMITTED ON SEPARATE SHEET, HOWEVER |
| | PLEASE SEE 220.31B FOR REQUIRED LOAD |
| | CALCULATION FOR EXSITING DWELLING. |
| | PLEASE CORRELATE LOAD CALCS WITH PANEL |
| | SCHEDULE AND PLANS. |
| | PLEASE SEE 220.18 FOR DRYER LOAD. |
| | PANEL SCHEDULE TO INCLUDE AWG,OCP FOR |
| | ALL MIN CIRCUITS REQUIRED. |
| | SEE NOTE #3 PREVIOUS REVIEW. |
| | |
| | 3)NOTE: PLEASE SEE NOTES:4,5 PREVIOUS |
| | REVIEW. |
| | |
| | 4)NOTE: PLEASE SEE FBC CHAPTER 34 |
| | 3401.7.1.2.1 PLEASE INDICATE NEW OR |
| | EXISTING SD'S AND GFI RECEPTS IN EXIST- |
| | -ING DWELLING TO MEET CODE. |
| | SD'D REQUIRED INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS. NFPA-72 8-1.4.1.6.2 |
| | |
| | 5)NOTE: PLEASE SEE FS 553.80(2)(B) |
| | ATTACHED WITH RESPECT TO DESIGN PROFESS- |
| | -IONAL. THIS IS ONLY A NOTICE GIVEN AT |
| | THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |