Plan Review Notes
Plan Review Notes For Permit 03121592
Permit Number 03121592
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-08 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH ORIG
 SIGNATURE, DATE AND SEAL BY THE ARCH OF
 RECORD. PER FS 481.221 AND FAC 61G1-16.
 -004.
  
 2)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 PER NEC 220.3C-1
 NEW AND EXISTING.
  
 3)NOTE: PLEASE PROVIDE PANEL SCHEDULE
 WITH NEW MIN CIRCUITS, AWG AND OCP.
 PLEASE SEE 210.52D AND 210.11C3 FOR MIN
 REQ'D FOR BATH(S).
  
  
 4)NOTE: PLEASE SEE SERVICE, SHOWN WITH
 EXST METER , BUT SERVICE IS BEING
 SHOWN AS NEW? PLEASE ALSO SEE 225A DISC
 ON THE LOAD SIDE OF PANEL?? PLEASE
 CLARIFY. PLEASE SUBMIT A COMPLETED RISER
 DIAGRAM. PLEASE SUBMIT AIC RATING IF
 SERVICE IS NEW? 110.9/ 215.5
  
 5)NOTE: PLEASE SEE THAT NEW ROOM IS
 SHOWING ONLY "J" BOXES ON CEILINGS.
 PLEASE SEE THAT A MIN LT WILL BE REQ'D
 TO BE INSTALLED FOR RM AT TIME OF FINAL.
 210.70 NEC AND LS-101
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]