| Plan Review Notes For Permit 03121592 |
| Permit Number |
03121592 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-01-08 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH ORIG | | | SIGNATURE, DATE AND SEAL BY THE ARCH OF | | | RECORD. PER FS 481.221 AND FAC 61G1-16. | | | -004. | | | | | | 2)NOTE: PLEASE PROVIDE LOAD CALCULATIONS | | | PER NEC 220.3C-1 | | | NEW AND EXISTING. | | | | | | 3)NOTE: PLEASE PROVIDE PANEL SCHEDULE | | | WITH NEW MIN CIRCUITS, AWG AND OCP. | | | PLEASE SEE 210.52D AND 210.11C3 FOR MIN | | | REQ'D FOR BATH(S). | | | | | | | | | 4)NOTE: PLEASE SEE SERVICE, SHOWN WITH | | | EXST METER , BUT SERVICE IS BEING | | | SHOWN AS NEW? PLEASE ALSO SEE 225A DISC | | | ON THE LOAD SIDE OF PANEL?? PLEASE | | | CLARIFY. PLEASE SUBMIT A COMPLETED RISER | | | DIAGRAM. PLEASE SUBMIT AIC RATING IF | | | SERVICE IS NEW? 110.9/ 215.5 | | | | | | 5)NOTE: PLEASE SEE THAT NEW ROOM IS | | | SHOWING ONLY "J" BOXES ON CEILINGS. | | | PLEASE SEE THAT A MIN LT WILL BE REQ'D | | | TO BE INSTALLED FOR RM AT TIME OF FINAL. | | | 210.70 NEC AND LS-101 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|