2004-01-06 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTE #2, WE ARE NOW
 UNDER THE 2002 NEC.
  
 2)NOTE: PLEASE SEE NOTE #17, MENTIONS
 210.12 REQUIREMENT. WE ARE NOW UNDER
 THE 2002 NEC WHICH CHANGED 210.12.
 PLEASE ADJUST.
  
 3)NOTE: PLEASE VERIFY OCP SHOWN FOR
 5 KW AHU. SHOWN EXCEEDING MAX OCP.
  
 4)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS. SPACING TO MEET 2',6',12' RULE.
  
 5)NOTE: PLANS SHOWS, A NEW 60A J-BOX??
 PLEASE CLARIFY??
  
 6)NOTE: PLEASE NOTE, WATER HEATER IS
 SHOWN BEING INSTALLED IN EXIST CLOSET,
 PLEASE PROVIDE NOTE TO MEET 422.17
  
 7)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 A 200A MAIN DISC AND A 200A MCB PANEL?
 PLEASE SEE THAT THIS IS PERMNITTED BY
 CODE , HOWEVER IT IS NOT REQ'D. IF SHOWN
 , THEN IT WILL BE REQ'D TO BE INSTALLED.
 SAME COMMENT FOR FOOTER STEEL AS PART
 OF GE SYSTEM. EXISTING BLDG ARE NOT
 REQ'D TO HAVE FOOTER STEEL , BUT IF
 SHOWN, THEN FOOTER WILL BE REQD'.
  
 8)NOTE: PLEASE ADJUST VALUE FOR SCOPE
 OF WORK SHOWN AND APPLIED FOR. PER
 104.6.5 FBC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW