| Date |
Text |
| 2004-01-06 00:00:00 | ************* UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE NOTE #2, WE ARE NOW |
| | UNDER THE 2002 NEC. |
| | |
| | 2)NOTE: PLEASE SEE NOTE #17, MENTIONS |
| | 210.12 REQUIREMENT. WE ARE NOW UNDER |
| | THE 2002 NEC WHICH CHANGED 210.12. |
| | PLEASE ADJUST. |
| | |
| | 3)NOTE: PLEASE VERIFY OCP SHOWN FOR |
| | 5 KW AHU. SHOWN EXCEEDING MAX OCP. |
| | |
| | 4)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS. SPACING TO MEET 2',6',12' RULE. |
| | |
| | 5)NOTE: PLANS SHOWS, A NEW 60A J-BOX?? |
| | PLEASE CLARIFY?? |
| | |
| | 6)NOTE: PLEASE NOTE, WATER HEATER IS |
| | SHOWN BEING INSTALLED IN EXIST CLOSET, |
| | PLEASE PROVIDE NOTE TO MEET 422.17 |
| | |
| | 7)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS |
| | A 200A MAIN DISC AND A 200A MCB PANEL? |
| | PLEASE SEE THAT THIS IS PERMNITTED BY |
| | CODE , HOWEVER IT IS NOT REQ'D. IF SHOWN |
| | , THEN IT WILL BE REQ'D TO BE INSTALLED. |
| | SAME COMMENT FOR FOOTER STEEL AS PART |
| | OF GE SYSTEM. EXISTING BLDG ARE NOT |
| | REQ'D TO HAVE FOOTER STEEL , BUT IF |
| | SHOWN, THEN FOOTER WILL BE REQD'. |
| | |
| | 8)NOTE: PLEASE ADJUST VALUE FOR SCOPE |
| | OF WORK SHOWN AND APPLIED FOR. PER |
| | 104.6.5 FBC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW, IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |