Plan Review Notes
Plan Review Notes For Permit 03121545
Permit Number 03121545
Review Stop B
Sequence Number 2
Notes
Date Text
2004-01-20 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS,WINDOWS
 GLASS BLOCK, MULLIONS, ROOF TILE AND
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DON'T PROVIDE 2" MIN. EMBEDMENT. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE ENGINEERING CALCS FOR TRUSS
 CONNECTORS AND NUMBER OF FASTENERS
 SINCE VALUES ARE DIFFERENT THAN THOSE
 TESTED AND PUBLISHED BY USP TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001 REGARDING
 STEEL STRESS LIMITATIONS.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-REVISE DETAIL A/4. WHERE ARE TABLES
 6 AND 8 TAKEN FROM?. WE USE FBC 2001
 AND ASCE 7-98.SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 5-SHEET #7: A)REVISE DESIGN PRESSURES AT
 EXTERIOR OPENINGS. SEE TABLES 1606.2B
 AND 1606.2E FBC 2001.
 B)DESIGN PRESSURES SHOWN ON THIS DRAWING
 DON'T MATCH THOSE ON SHEET 3. REVISE
 C)REVISE NOTES ON FLOOR PLAN AND ROOF
 PLAN. MAKE SURE NOTES RELATE TO CONCRE
 TE BEAM AND NOT WOOD BEAM. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON ELEVATION DON'T MATCH
 WINDOW SCHEDULE. REVISE AS REQUIRED.