| 2004-01-20 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR ALL DOORS,WINDOWS |
| | GLASS BLOCK, MULLIONS, ROOF TILE AND |
| | STRUCTURAL CONNECTORS. |
| | 2-REVISE DETAIL E/4. FASTENER SPECIFIED |
| | DON'T PROVIDE 2" MIN. EMBEDMENT. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 3-PROVIDE ENGINEERING CALCS FOR TRUSS |
| | CONNECTORS AND NUMBER OF FASTENERS |
| | SINCE VALUES ARE DIFFERENT THAN THOSE |
| | TESTED AND PUBLISHED BY USP TO COMPLY |
| | WITH SEC. 1609.4.3 FBC 2001 REGARDING |
| | STEEL STRESS LIMITATIONS.SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 4-REVISE DETAIL A/4. WHERE ARE TABLES |
| | 6 AND 8 TAKEN FROM?. WE USE FBC 2001 |
| | AND ASCE 7-98.SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 5-SHEET #7: A)REVISE DESIGN PRESSURES AT |
| | EXTERIOR OPENINGS. SEE TABLES 1606.2B |
| | AND 1606.2E FBC 2001. |
| | B)DESIGN PRESSURES SHOWN ON THIS DRAWING |
| | DON'T MATCH THOSE ON SHEET 3. REVISE |
| | C)REVISE NOTES ON FLOOR PLAN AND ROOF |
| | PLAN. MAKE SURE NOTES RELATE TO CONCRE |
| | TE BEAM AND NOT WOOD BEAM. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | D)WINDOWS SHOWN ON ELEVATION DON'T MATCH |
| | WINDOW SCHEDULE. REVISE AS REQUIRED. |