2004-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-STORM SHUTTERS: A)REVISE KEY PLAN AND
 INSTALLATION SCHEDULE. NEED EMERGENCY
 EGRESS THAT COMPLIES WITH SECTION
 1005.4.5 FBC 2001.
 B)CLEARLY INDICATE ANCHOR TYPE & SPACING
 TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE, CONNECTION
 TYPE, PANEL SPAN AND STRUCTURE TO BE
 ATTACHED TO (MASONRY OR CONCRETE). SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW: NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE (FBC APPROVAL IS PENDING).
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
 H)TRUSS CONNECTORS.
  
 4-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES. SEE FAC SECTION
 61G1-16004.
 5-1 HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO MATCH SUCH ASSEMBLY.
 SPECIFY ALL COMPONENTS REQUIRED TO
 OBTAIN THE REQUIRED FIRE RATING. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER AND EMBEDMENT
 REQUIRED. SEC. 104.2.1.2 CITY AMENDM.
 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001 REGARDING THE STEEL
 STRESS.
 B)SPECIFY USP RT SIZES TO VERIFY VALUE
 SPECIFIED ON CATALOGUE.
 C)KEEP IN MIND THAT ALL CONNECTORS NEED
 TO HAVE PRODUCT APPROVAL.
 8-ENGINEER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 9-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 10-SHEET #7: A)CLARIFY WHERE IS USP
 EHUH 28-3 TAKEN FROM?. UNABLE TO FIND
 THIS CONNECTOR IN 2003 USP CATALOGUE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 B)MISSING SPECIFICATIONS FOR ONE END OF
 GIRDER TRUSS AT REAR PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)REAR ELEVATION: CLARIFY CALCULATIONS
 FOR DESIGN PRESSURES WITH DIFFERENT
 SIZES.
 **ALSO, SHOW TYPE OF WINDOWS. THEY ARE
 SHOWN AS FIXED WINDOWS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.