| 2004-01-16 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR: ALL DOOR/WINDOW |
| | TYPES, GLASS BLOCK, MULLIONS, ROOF |
| | TILE AND STRUCTURAL CONNECTORS. |
| | 2-DETAIL E/4: REVISE FASTENER SIZE TO |
| | ACHIEVE 2" MIN. EMBEDMENT. ALSO,REVISE |
| | NOTES ON DWG #2 TO BE CONSISTENT. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 3-PROVIDE ENGINEERING CALCULATIONS FOR |
| | FASTENERS SPECIFIED ON TRUSS ANCHOR |
| | SCHEDULE TO SHOW COMPLIANCE WITH SEC. |
| | 1609.4.3 FBC 2001 WHICH DOESN'T ALLOW |
| | STEEL STRESS TO BE INCREASED. |
| | 4-DETAIL A/4: ROOF TILE FASTENERS NOTES |
| | REFER TO TABLES 6 AND 8. CLARIFY WHERE |
| | ARE THESE TABLES COMING FROM? SEE FBC |
| | 2001 OR ASCE 7-98. |
| | 5-SHEET A-7: A)REVISE DESIGN PRESSURES |
| | AT EXTEIOR OPENINGS. SEE TABLES |
| | 1606.2B AND 1606.2E FBC 2001. PROVIDE |
| | ENGINEERING CALCS FOR DIFFERENT DESIGN |
| | PRESSURES. SECTION 104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | B)DESIGN PRESSURES SHOWN ON SHEET 3B AND |
| | SHEET 7 DON'T MATCH. REVISE AS REQ'D. |
| | C)REVISE REAR PORCH FLOOR PLAN AND ROOF |
| | FRAMING PLAN NOTES AND TRUSS ANCHOR TO |
| | MATCH. NOTE THAT BEAM WAS CHANGED FROM |
| | GIRDER TRUSS TO CONCRETE BEAM. REVISE |
| | TRUSS CONNECTOR ACCORDINGLY. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | D)WNDOWS SHOWN ON ELEVATION DON'T MATCH |
| | THOSE SPECIFIED ON WINDOW SCHEDULE. |
| | REVISE AS REQUIRED. |