| Plan Review Notes For Permit 03121516 |
| Permit Number |
03121516 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-21 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | | PRODUCT APPROVAL FOR ALL DOORS,WINDOWS | | | GLASS BLOCK, MULLIONS, ROOF TILE AND | | | STRUCTURAL CONNECTORS. | | | 2-REVISE DETAIL E/4. FASTENER SPECIFIED | | | DOESN'T PROVIDE THE 2" MIN. EMBEDMENT. | | | 3-PROVIDE ENGINEERING CALCULATIONS FOR | | | TRUSS FASTENERS THAT ARE DIFFERENT | | | FROM THOSE TESTED AND PUBLISHED BY | | | USP TO COMPLY WITH SECTION 1609.4.3 | | | FBC 2001. | | | 4-REVISE DETAIL A/4. WHERE ARE TABLES 6 | | | AND 8 CITED FROM?. SEE ASCE 7-98 OR | | | FBC 2001. | | | 5-SHEET #7: A)REVISE DESIGN PRESSURES. | | | SEE TABLES 1606.2B AND 1606.2E FBC. | | | B)DESIGN PRESSURES SHOWN DON'T MATCH | | | THOSE SHOWN ON SHEET 3. | | | C)REVISE REAR PORCH FLOOR PLAN AND ROOF | | | PLAN NOTES REGARDING WOOD BEAM SINCE | | | IT WAS CHANGED TO CONCRETE BEAM. | | | D)WINDOWS SHOWN ON EXTERIOR ELEVATION | | | DON'T MATCH WINDOW SCHEDULE. |
|