| 2004-01-20 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR ALL WINDOW/DOOR |
| | TYPES, GLASS BLOCK, MULLIONS, ROOF |
| | TILE AND STRUCTURAL CONNECTORS. |
| | 2-REVISE DETAIL E/4. FASTENER SPECIFIED |
| | DOESN'T PROVIDE 2" MIN. EMBEDMENT. SEC |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 3-PROVIDE ENGINEERING CALCS FOR NUMBER |
| | OF FASTENERS SPECIFIED FOR TRUSS |
| | ANCHORS SINCE THEY DIFFER FROM THOSE |
| | TESTED AND PUBLISHED BY USP TO COMPLY |
| | WITH SEC. 1609.4.3 FBC 2001 REGARDING |
| | THE STEEL STRESS.SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 4-REVISE DETAIL A/4. WHERE ARE TABLES 6 |
| | AND 8 TAKEN FROM?. WE USE ASC7 7-98 OR |
| | FBC 2001. |
| | 5-SHEET A-7: A)REVISE DESIGN PRESSURES @ |
| | EXTERIOR OPENINGS. SEE TABLES 1606.2B |
| | AND 1606.2E FBC 2001. |
| | B)DESIGN PRESSURES SHOWN ON SHEET 7 AND |
| | SHEET 3 DON'T MATCH. REVISE AS REQ'D. |
| | C)REVISE REAR PORCH FLOOR PLAN AND ROOF |
| | FRAMING PLAN. CHANGE NOTES RELATED TO |
| | WOOD BM. SINCE IT WAS CHANGED TO CONC. |
| | BEAM. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | D)WINDOWS SHOWN ON ELEVATION DON'T MATCH |
| | THOSE SPECIFIED ON WINDOW SCHEDULE. |