| Plan Review Notes For Permit 03121490 |
| Permit Number |
03121490 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-21 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | | PRODUCT APPROVAL FOR ALL DOORS,WINDOWS | | | ROOF TILE, GLASS BLOCK, MULLIONS AND | | | STRUCTURAL CONNECTORS. | | | 2-REVISE DETAIL E/4. FASTENER SPECIFIED | | | DOESN'T PROVIDE 2" MIN. EMBEDMENT. | | | 3-PROVIDE ENGINEERING CALCULATIONS FOR | | | FASTENERS USED IN TRUSS ANCHOR SCHED. | | | SINCE THEY ARE DIFFERENT FROM THOSE | | | TESTED AND PUBLISHED BY USP TO COMPLY | | | WITH SEC. 1609.4.3 FBC 2001 REGARDING | | | STEEL STRESS LIMITATIONS. | | | 4-REVISE DETAIL A/4. CITED TABLES 6 & 8 | | | ARE NOT FROM FBC 2001 OR ASCE 7-98. | | | 5-SHEET #7: A)REVISE DESIGN PRESSURES. | | | SEE TABLES 1606.2B & 1606.2E FBC 2001. | | | B)DESIGN PRESSURES DON'T MATCH THOSE | | | SHOWN ON SHEET #3. | | | C)REVISE ALL NOTES ON PORCH FLOOR PLAN | | | AND ROOF PLAN REGARDING WOOD BEAM. | | | IT WAS CHANGED TO CONCRETE BEAM. | | | D)WINDOWS SHOWN ON EXTERIOR ELEVATION | | | DON'T MATCH WINDOW SCHEDULE. |
|